9.2 Details of Function Codes
9-47
Chap. 9
FUNCTI
ON C
O
DE
S
If P99 (Motor characteristics) is set to 1 (HP motors):
Rated current (A)
Setting range (kW)
If P99 (Motor characteristics) is set to:
Power
supply
voltage
Function code
P02
Applicable motor
rating (kW)
1
0.01 to 0.10
0.1
0.34
0.11 to 0.12
0.12
0.71
0.13 to 0.25
0.25
1.40
0.26 to 0.50
0.5
2.00
0.51 to 1.00
1
3.00
1.01 to 2.00
2
5.80
2.01 to 3.00
3
7.90
3.01 to 5.00
5
12.60
5.01 to 7.50
7.5
18.6
200 V
7.51 to 10.00
10
25.3
0.01 to 0.10
0.1
0.35
0.11 to 0.12
0.12
0.36
0.13 to 0.25
0.25
0.70
0.26 to 0.50
0.5
1.00
0.51 to 1.00
1
1.50
1.01 to 2.00
2
2.90
2.01 to 3.00
3
4.00
3.01 to 5.00
5
6.30
5.01 to 7.50
7.5
9.30
400 V
7.51 to 10.00
10
12.7
NOTE: Values in the Rated current column are based on 60 Hz. If the base frequency and/or
rated voltage differ, change the setting of P02.
H04
Retry (No. of retries)
H05
Retry (Latency time)
To automatically exit from the alarm status and restart the inverter, use the retry functions.
In doing so, the inverter automatically exits from Alarm mode and restarts without issuing a
block alarm even if it has entered the forced Alarm mode. If the inverter has entered Alarm
mode during retry (specified by function code H04), it issues a block alarm and does not
exit Alarm mode for restarting.
Listed below are the recoverable alarm statuses of the inverter.
Alarm Status
LED monitor display
Instantaneous overcurrent
protection
0C1, 0C2
or
0C3
Overvoltage protection
0U1, 0U2
or
0U3
Heat sink overheated
0H1
Motor overheated
0H4
Braking resistor overheated
dbH
Motor overloaded
0L1
Inverter overloaded
0LU
Settings and operations
Retry times (H04)
Set the number of retry times for automatic exit from Alarm mode. If the inverter has
entered Alarm mode during the retry times specified, the inverter issues a block alarm and
does not exit alarm mode for restarting.
- Data setting range: 1 to 10 (times) (If 0 is set, the "retry" operation will not be activated.)
Содержание frenic mini series
Страница 1: ...USER S MANUAL Fuji Electric Co Ltd MEH446...
Страница 2: ...Compact Inverter User s Manual...
Страница 60: ...4 2 4 2 Drive Frequency Command Generator Figure 4 1 Block Diagram for Drive Frequency Command Generator...
Страница 62: ...4 4 4 3 Drive Command Generator Figure 4 2 Drive Command Generator...
Страница 66: ...4 8 Figure 4 3 d Terminal Command Decoder ORing with Link Commands Ignoring Link Commands...
Страница 68: ...4 10 4 5 Digital Output Selector Figure 4 4 Digital Output Signal Selector...
Страница 70: ...4 12 4 6 Analog Output FMA Selector Figure 4 5 Analog Output FMA Selector...
Страница 72: ...4 14 4 7 Drive Command Controller Figure 4 6 Drive Command Controller and Related Part of the Inverter...
Страница 74: ...4 16 4 8 PID Frequency Command Generator Figure 4 7 PID Frequency Command Generator...
Страница 81: ...Part 3 Peripheral Equipment and Options Chapter 6 SELECTING PERIPHERAL EQUIPMENT...
Страница 109: ...Part 4 Selecting Optimal Inverter Model Chapter 7 SELECTING OPTIMAL MOTOR AND INVERTER CAPACITIES...
Страница 124: ...Part 5 Specifications Chapter 8 SPECIFICATIONS Chapter 9 FUNCTION CODES...
Страница 134: ...8 3 Common Specifications 8 9 Chap 8 SPECIFICATIONS 8 3 Common Specifications...
Страница 135: ...8 10...
Страница 257: ...App H Replacement Information A 33 App FVR C11S vs FRENIC Mini...
Страница 261: ...Glossary This glossary explains the technical terms that are frequently used in this manual...