![Fuji Electric frenic mini series Скачать руководство пользователя страница 182](http://html1.mh-extra.com/html/fuji-electric/frenic-mini-series/frenic-mini-series_user-manual_2341845182.webp)
9.2 Details of Function Codes
9-25
Chap. 9
FUNCTI
ON C
O
DE
S
F37
Load Selection/Auto Torque Boost/Auto Energy Saving Operation
Allows you to select the load type and enable/disable auto torque boost and auto energy
saving operation. The load selection enables an optimal V/f pattern to be selected.
Load selection
There are two different properties of loads--the torque load which is reversely proportional
to the square of speed and the constant torque load. You can select a V/f pattern optimized
to the load property. Refer to the figure in the descriptions for function code F09 for details.
Auto torque boost
This feature optimizes the output voltage automatically to the motor and its load. Even if
the load varies, the inverter can maintain the exciting current fed to the motor so as not to
over-excite the motor. The maximum output torque of the motor will be increased.
• If the automatic torque boost is enabled (F37 = 2 or 5), function code F09 will
be ignored.
• If either the torque reversely proportional to the square of the speed or the
constant torque is selected (F37 = 0, 1, 3, or 4), it is necessary to modify the
F09 data (Torque boost: 0.0 to 20.0%).
• If a motor parameter is a special one or the rigidity of the load is not sufficient,
lowering the maximum output torque or unstable operation may sometimes
result. To avoid this happening, disable the automatic torque boost (F37 = 0 or
1) and set the torque boost with F09 manually.
Auto energy saving operation
This feature controls the terminal voltage of the motor automatically to minimize the motor
power loss. (Note that this feature may not be effective depending upon the motor
characteristics. Check the properties before using this feature.)
The inverter enables this feature for constant speed operation only. During acceleration and
deceleration, the inverter will run with manual or automatic torque boost, depending on the
data setting of function code F37. If auto energy-saving operation is enabled, the response
to a change in motor speed may be slow. Do not use this feature for a system that requires
quick acceleration and deceleration.
Set F37
to:
Load selection
Auto torque
boost
Auto energy
saving
F09
Remarks
0
Variable torque
Disabled
Disabled
Enabled
1
Constant torque
Disabled
Disabled
Enabled
2
Not available
Enabled
Disabled
Disabled
3
Variable torque
Disabled
Enabled
Enabled
4
Constant torque
Disabled
Enabled
Enabled
5
Not available
Enabled
Enabled
Disabled
The auto energy-saving
feature is enabled only for
constant speed operation.
During acceleration/
deceleration, the inverter
runs with manual or
automatic torque boost.
When using the auto torque boost or energy-saving feature, you need to set the
rated voltage of the motor to F05 (Voltage at the base frequency) and the motor
parameters to the motor-related P codes.
Содержание frenic mini series
Страница 1: ...USER S MANUAL Fuji Electric Co Ltd MEH446...
Страница 2: ...Compact Inverter User s Manual...
Страница 60: ...4 2 4 2 Drive Frequency Command Generator Figure 4 1 Block Diagram for Drive Frequency Command Generator...
Страница 62: ...4 4 4 3 Drive Command Generator Figure 4 2 Drive Command Generator...
Страница 66: ...4 8 Figure 4 3 d Terminal Command Decoder ORing with Link Commands Ignoring Link Commands...
Страница 68: ...4 10 4 5 Digital Output Selector Figure 4 4 Digital Output Signal Selector...
Страница 70: ...4 12 4 6 Analog Output FMA Selector Figure 4 5 Analog Output FMA Selector...
Страница 72: ...4 14 4 7 Drive Command Controller Figure 4 6 Drive Command Controller and Related Part of the Inverter...
Страница 74: ...4 16 4 8 PID Frequency Command Generator Figure 4 7 PID Frequency Command Generator...
Страница 81: ...Part 3 Peripheral Equipment and Options Chapter 6 SELECTING PERIPHERAL EQUIPMENT...
Страница 109: ...Part 4 Selecting Optimal Inverter Model Chapter 7 SELECTING OPTIMAL MOTOR AND INVERTER CAPACITIES...
Страница 124: ...Part 5 Specifications Chapter 8 SPECIFICATIONS Chapter 9 FUNCTION CODES...
Страница 134: ...8 3 Common Specifications 8 9 Chap 8 SPECIFICATIONS 8 3 Common Specifications...
Страница 135: ...8 10...
Страница 257: ...App H Replacement Information A 33 App FVR C11S vs FRENIC Mini...
Страница 261: ...Glossary This glossary explains the technical terms that are frequently used in this manual...