9-10
y codes: Link Functions
Code
Name
Data setting range
Incre-
mental
unit
Unit
Change
when
running
Data
copy
Default
setting
y01
RS485
Communication
(Station address)
1 to 255
(Broadcast:(0: RTU), (99: FGI-BUS))
1
—
N
Y
1
y02
(Mode selection on no
response error)
0: Immediate trip and alarm
E 8
1: Trip and alarm
E 8
after running for the
period of the timer set by y03
2: Retry during the period of the timer set by
y03. If retry fails, trip and alarm
E 8
3: Continue to run
—
—
Y
Y
0
y03
(Timer) 0.0 to 60.0
0.1
sec
Y
Y
2.0
y04
(Baud rate) 0: 2400 bps
1: 4800 bps
2: 9600 bps
3: 19200 bps
—
—
Y
Y
3
y05
(Data length) 0: 8 bits
1: 7 bits
—
—
Y
Y
0
y06
(Parity check) 0: None
1: Even parity
2: Odd parity
—
—
Y
Y
0
y07
(Stop bits) 0: 2 bits
1: 1 bit
—
—
Y
Y
0
y08
(No response error
detection time)
0 (No detection), 1 to 60
1
sec
Y
Y
0
y09
(Response interval) 0.00 to 1.00
0.01 sec
Y
Y
0.01
y10
(Protocol selection) 0: Modbus RTU protocol
1: SX protocol (Loader protocol)
2: Fuji general-purpose inverter protocol
—
—
Y
Y
1
y99
Link Function for
Supporting Data Input
Frequency setting
Run command
0:
by H30
by H30
1:
from RS485
by H30
2:
by H30
from RS485
3:
from RS485
from RS485
—
—
Y
N
0
*The table below lists the factory settings of "Fuji's standard torque boost," "Nominal rated current of Fuji's
standard motor," and "Nominal rated capacity of Fuji's standard motor" in the "Default setting" column of the
above tables.
Fuji's standard value
torque boost (%)
Nominal rated current of Fuji's
standard motor (A)
Nominal rated capacity
of Fuji's standard motor
(kW)
Rated
input
voltage
Applicable motor
rating
(kW)
Function code F09
Function codes F11, E34, and P03
Function code P02
0.1
8.4
0.61
0.1
0.2
8.4
1.16
0.2
0.4
7.1
2.13
0.4
0.75
6.8
3.36
0.75
1.5
6.8
5.87
1.5
2.2
6.8
8.80
2.2
200 V
3.7, 4.0
5.5
14.38
3.7, 4.0
0.4
7.1
1.07
0.4
0.75
6.8
1.68
0.75
1.5
6.8
2.94
1.5
2.2
6.8
4.40
2.2
400V
3.7, 4.0
5.5
7.20
3.7, 4.0
Содержание frenic mini series
Страница 1: ...USER S MANUAL Fuji Electric Co Ltd MEH446...
Страница 2: ...Compact Inverter User s Manual...
Страница 60: ...4 2 4 2 Drive Frequency Command Generator Figure 4 1 Block Diagram for Drive Frequency Command Generator...
Страница 62: ...4 4 4 3 Drive Command Generator Figure 4 2 Drive Command Generator...
Страница 66: ...4 8 Figure 4 3 d Terminal Command Decoder ORing with Link Commands Ignoring Link Commands...
Страница 68: ...4 10 4 5 Digital Output Selector Figure 4 4 Digital Output Signal Selector...
Страница 70: ...4 12 4 6 Analog Output FMA Selector Figure 4 5 Analog Output FMA Selector...
Страница 72: ...4 14 4 7 Drive Command Controller Figure 4 6 Drive Command Controller and Related Part of the Inverter...
Страница 74: ...4 16 4 8 PID Frequency Command Generator Figure 4 7 PID Frequency Command Generator...
Страница 81: ...Part 3 Peripheral Equipment and Options Chapter 6 SELECTING PERIPHERAL EQUIPMENT...
Страница 109: ...Part 4 Selecting Optimal Inverter Model Chapter 7 SELECTING OPTIMAL MOTOR AND INVERTER CAPACITIES...
Страница 124: ...Part 5 Specifications Chapter 8 SPECIFICATIONS Chapter 9 FUNCTION CODES...
Страница 134: ...8 3 Common Specifications 8 9 Chap 8 SPECIFICATIONS 8 3 Common Specifications...
Страница 135: ...8 10...
Страница 257: ...App H Replacement Information A 33 App FVR C11S vs FRENIC Mini...
Страница 261: ...Glossary This glossary explains the technical terms that are frequently used in this manual...