9-36
Service life alarm--(LIFE)
(Function code data = 30)
This signal is turned ON when it is judged that the service life of any of capacitors
(capacitor in the DC link circuit and electrolytic capacitors on the printed circuit boards)
and cooling fan has expired.
The judgement level for service life are as follows. This information can be checked in
Menu #5 "Maintenance information" of Programming mode.
Parts
Judgement level for service life
Capacitor in the DC link
circuit
Capacity: Max. 85% of factory default
Capacitor/s on the
printed circuit boards
Accumulated run time: 61,000 hours or more
Cooling fan
Accumulated run time: 61,000 hours or more (1.5 to 3.7 kW
models) (Based on the assumption that the inverter runs in an
ambient temperature of 40°C)
This facility provides tentative information for service life of the parts. If this signal is
issued, check the service life of these parts in your system according to the maintenance
procedure to determine whether the parts should be replaced or not. To maintain stable and
reliable operation and avoid unexpected failures, daily and periodic maintenance must be
performed. For details, refer to the FRENIC-Mini Instruction Manual, Chapter 7
"MAINTENANCE AND INSPECTION."
Inverter running--(RUN2)
(Function code data = 35)
This signal is turned ON when the main switching circuit (IGBT gates) is activated; it is
OFF when it is not activated.
Overload prevention control--(OLP)
(Function code data = 36)
This signal is turned ON when the overload prevention facility is activated if the frequency
drop rate comes to be the setting specified by function code H70. The minimum ON-
duration is 100 ms.
For details of the overload prevention control, refer to the descriptions of function
code H70.
Current detection--(ID)
(Function code data = 37)
This signal is turned ON when the output current exceeds the operation level specified by
function code E34 and stays in this status for the duration specified by function code E35
(on delay timer). The minimum ON-duration is 100 ms.
If the output current drops to 90% of the operation level, this signal is turned OFF.
This signal can be used as a reference for determining the running speed in the operation of
load machinery or system, by monitoring the inverter's load state.
Function codes E34 and E35 are effective not only for the current detection (ID),
but often also for the overload early warning (OL) and low level current detection
(IDL).
Содержание frenic mini series
Страница 1: ...USER S MANUAL Fuji Electric Co Ltd MEH446...
Страница 2: ...Compact Inverter User s Manual...
Страница 60: ...4 2 4 2 Drive Frequency Command Generator Figure 4 1 Block Diagram for Drive Frequency Command Generator...
Страница 62: ...4 4 4 3 Drive Command Generator Figure 4 2 Drive Command Generator...
Страница 66: ...4 8 Figure 4 3 d Terminal Command Decoder ORing with Link Commands Ignoring Link Commands...
Страница 68: ...4 10 4 5 Digital Output Selector Figure 4 4 Digital Output Signal Selector...
Страница 70: ...4 12 4 6 Analog Output FMA Selector Figure 4 5 Analog Output FMA Selector...
Страница 72: ...4 14 4 7 Drive Command Controller Figure 4 6 Drive Command Controller and Related Part of the Inverter...
Страница 74: ...4 16 4 8 PID Frequency Command Generator Figure 4 7 PID Frequency Command Generator...
Страница 81: ...Part 3 Peripheral Equipment and Options Chapter 6 SELECTING PERIPHERAL EQUIPMENT...
Страница 109: ...Part 4 Selecting Optimal Inverter Model Chapter 7 SELECTING OPTIMAL MOTOR AND INVERTER CAPACITIES...
Страница 124: ...Part 5 Specifications Chapter 8 SPECIFICATIONS Chapter 9 FUNCTION CODES...
Страница 134: ...8 3 Common Specifications 8 9 Chap 8 SPECIFICATIONS 8 3 Common Specifications...
Страница 135: ...8 10...
Страница 257: ...App H Replacement Information A 33 App FVR C11S vs FRENIC Mini...
Страница 261: ...Glossary This glossary explains the technical terms that are frequently used in this manual...