![Fuji Electric frenic mini series Скачать руководство пользователя страница 198](http://html1.mh-extra.com/html/fuji-electric/frenic-mini-series/frenic-mini-series_user-manual_2341845198.webp)
9.2 Details of Function Codes
9-41
Chap. 9
FUNCTI
ON C
O
DE
S
9.2.3
C Codes (Control Functions of Frequency)
C01 to C03
Jump Frequencies 1, 2 and 3
C04
Jump Frequency Band
These function codes enable the inverter to jump up to three different points on the output
frequency in order to skip the resonance frequency caused by the motor drive frequency and
natural frequency of the driven mechanism.
- During acceleration, the moment the set frequency reaches the bottom of the set jump
frequency band, the inverter keeps the output at that bottom frequency until the output
frequency reaches the upper limit and proceeds with the acceleration until the next set
point is reached or set speed is reached.
During deceleration, the inverter processes the set jump frequency band in reverse to the
acceleration curve. Refer to the left-hand figure below.
- When the set jump frequency bands overlap, the overlapped band is ignored, the inverter
takes the lowest frequency within the overlapped bands as the bottom frequency and the
highest as the peak. Refer to the right-hand figure below.
Jump frequencies 1,2 and 3 (C01, C02 and C03)
Set the center of the jump frequency band.
- Data setting range: 0.0 to 400.0 (Hz) (Setting to 0.0 results in no jump band)
Jump frequency band (C04)
Set the width of the jump frequency band.
- Data setting range: 0.0 to 30.0 (Hz) (Setting to 0.0 results in no jump band)
C05 to C11
Multi-step Frequency Settings 1 to 7
These function codes set frequencies required for driving the motor at frequencies 1 to 7.
- Data setting range: 0.00 to 400.00 (Hz)
- Turning terminal commands (SS1), (SS2) and (SS4) ON/OFF selectively switches the set
frequency of the inverter in 7 steps. For details of the terminal function assignment, refer
to the descriptions for function codes E01 to E03 "Command Assignment to Terminals
[X1] to [X3]."
For the multi-step frequency driving, refer to Chapter 4, Section 4.2 "Drive Frequency
Command Generator."
Содержание frenic mini series
Страница 1: ...USER S MANUAL Fuji Electric Co Ltd MEH446...
Страница 2: ...Compact Inverter User s Manual...
Страница 60: ...4 2 4 2 Drive Frequency Command Generator Figure 4 1 Block Diagram for Drive Frequency Command Generator...
Страница 62: ...4 4 4 3 Drive Command Generator Figure 4 2 Drive Command Generator...
Страница 66: ...4 8 Figure 4 3 d Terminal Command Decoder ORing with Link Commands Ignoring Link Commands...
Страница 68: ...4 10 4 5 Digital Output Selector Figure 4 4 Digital Output Signal Selector...
Страница 70: ...4 12 4 6 Analog Output FMA Selector Figure 4 5 Analog Output FMA Selector...
Страница 72: ...4 14 4 7 Drive Command Controller Figure 4 6 Drive Command Controller and Related Part of the Inverter...
Страница 74: ...4 16 4 8 PID Frequency Command Generator Figure 4 7 PID Frequency Command Generator...
Страница 81: ...Part 3 Peripheral Equipment and Options Chapter 6 SELECTING PERIPHERAL EQUIPMENT...
Страница 109: ...Part 4 Selecting Optimal Inverter Model Chapter 7 SELECTING OPTIMAL MOTOR AND INVERTER CAPACITIES...
Страница 124: ...Part 5 Specifications Chapter 8 SPECIFICATIONS Chapter 9 FUNCTION CODES...
Страница 134: ...8 3 Common Specifications 8 9 Chap 8 SPECIFICATIONS 8 3 Common Specifications...
Страница 135: ...8 10...
Страница 257: ...App H Replacement Information A 33 App FVR C11S vs FRENIC Mini...
Страница 261: ...Glossary This glossary explains the technical terms that are frequently used in this manual...