9.2 Details of Function Codes
9-59
Chap. 9
FUNCTI
ON C
O
DE
S
Gain (J03)
Sets the gain for the PID processor.
- Data setting range: 0.000 to 10.000
×
(times)
P (Proportional) control
An operation using an output
frequency proportional to deviation is
called P operation, which outputs an
operational amount proportional to
deviation, through it cannot eliminate
deviation alone.
Gain determines the system response level for the deviation in the P control. An increase in
gain speeds up response, an excessive gain can cause vibration, and a decrease in gain
delays response.
Integration time (J04)
Sets the integration time for the PID processor.
- Data setting range: 0.0 to 3600.0 (sec.)
I (Integral) control
The PID operation having the
proportional relationship of deviation
between the commanded (frequency)
rate (Hz/s) and control amounts is
called the I control. The I control
outputs the control amount proportional
to the integral amount of the deviation.
Therefore, it is effective for making the
feedback amount consistent with the
commanded one (such as frequency).
For the system whose deviation of
response rapidly changes, however, this
control cannot make the system react
quickly.
The effectiveness of I control is expressed by a parameter of integration time. The longer
the integration time, the slower the response. The reaction force of the system to an external
stimulus force becomes weak. The shorter integration time the faster response. Setting too
short integration time, however, makes the system tend to oscillate.
Содержание frenic mini series
Страница 1: ...USER S MANUAL Fuji Electric Co Ltd MEH446...
Страница 2: ...Compact Inverter User s Manual...
Страница 60: ...4 2 4 2 Drive Frequency Command Generator Figure 4 1 Block Diagram for Drive Frequency Command Generator...
Страница 62: ...4 4 4 3 Drive Command Generator Figure 4 2 Drive Command Generator...
Страница 66: ...4 8 Figure 4 3 d Terminal Command Decoder ORing with Link Commands Ignoring Link Commands...
Страница 68: ...4 10 4 5 Digital Output Selector Figure 4 4 Digital Output Signal Selector...
Страница 70: ...4 12 4 6 Analog Output FMA Selector Figure 4 5 Analog Output FMA Selector...
Страница 72: ...4 14 4 7 Drive Command Controller Figure 4 6 Drive Command Controller and Related Part of the Inverter...
Страница 74: ...4 16 4 8 PID Frequency Command Generator Figure 4 7 PID Frequency Command Generator...
Страница 81: ...Part 3 Peripheral Equipment and Options Chapter 6 SELECTING PERIPHERAL EQUIPMENT...
Страница 109: ...Part 4 Selecting Optimal Inverter Model Chapter 7 SELECTING OPTIMAL MOTOR AND INVERTER CAPACITIES...
Страница 124: ...Part 5 Specifications Chapter 8 SPECIFICATIONS Chapter 9 FUNCTION CODES...
Страница 134: ...8 3 Common Specifications 8 9 Chap 8 SPECIFICATIONS 8 3 Common Specifications...
Страница 135: ...8 10...
Страница 257: ...App H Replacement Information A 33 App FVR C11S vs FRENIC Mini...
Страница 261: ...Glossary This glossary explains the technical terms that are frequently used in this manual...