![Fuji Electric frenic mini series Скачать руководство пользователя страница 194](http://html1.mh-extra.com/html/fuji-electric/frenic-mini-series/frenic-mini-series_user-manual_2341845194.webp)
9.2 Details of Function Codes
9-37
Chap. 9
FUNCTI
ON C
O
DE
S
Low level current detection--(IDL)
(Function code data = 41)
This signal is turned ON when the output current drops below the operation level specified
by function code E34 and stays in this status for the duration specified by function code E35
(on delay timer).
If the output current exceeds the sum of the current level of operation and 5% of the rated
current of the inverter, then this signal is turned OFF.
Use this signal to indicate 0A output current due to a broken output wire, zero motor torque,
or any such factor undetectable by the inverter alarm facilities.
Function codes E34 and E35 are effective not only for the low level current
detection (IDL), but often also for the overload early warning (OL) and current
detection (ID).
Alarm relay contact output (for any fault)--(ALM)
(Function code data = 99)
This signal is turned ON if the protection facility is activated so that the inverter enters
Alarm mode.
In a system which monitors inverter alarm information through [30A, B, C] relay contacts,
make sure that function code data of E20 or E27 is set to 99.
E31
Frequency Detection (FDT) (Detection level)
Specifies an operating level for the set frequency detection signal. The hysteresis frequency
band between detection and release levels is 1.0 Hz.
- Data setting range: 0.0 to 400.0 (Hz)
E34
Overload Early Warning/Current Detection/Low Current Detection (Level)
E35
Overload Early Warning/Current Detection/Low Current Detection (Timer)
E34 and E35 set the operation level for overload early warning, current detection and low
current detection, and the timer count.
Operation Level (E34)
Sets the operation level for the motor overload early warning (OL), inverter output current
detection (ID), or low current output detection (IDL).
- Data setting range: Current value of 1 to 200% of the rated inverter current in units of
amperes.
Timer (E35)
Sets the timer for the inverter output current detection (ID) and low current output detection
(IDL).
- Data setting range: 0.01 to 60.00 (sec.)
Содержание frenic mini series
Страница 1: ...USER S MANUAL Fuji Electric Co Ltd MEH446...
Страница 2: ...Compact Inverter User s Manual...
Страница 60: ...4 2 4 2 Drive Frequency Command Generator Figure 4 1 Block Diagram for Drive Frequency Command Generator...
Страница 62: ...4 4 4 3 Drive Command Generator Figure 4 2 Drive Command Generator...
Страница 66: ...4 8 Figure 4 3 d Terminal Command Decoder ORing with Link Commands Ignoring Link Commands...
Страница 68: ...4 10 4 5 Digital Output Selector Figure 4 4 Digital Output Signal Selector...
Страница 70: ...4 12 4 6 Analog Output FMA Selector Figure 4 5 Analog Output FMA Selector...
Страница 72: ...4 14 4 7 Drive Command Controller Figure 4 6 Drive Command Controller and Related Part of the Inverter...
Страница 74: ...4 16 4 8 PID Frequency Command Generator Figure 4 7 PID Frequency Command Generator...
Страница 81: ...Part 3 Peripheral Equipment and Options Chapter 6 SELECTING PERIPHERAL EQUIPMENT...
Страница 109: ...Part 4 Selecting Optimal Inverter Model Chapter 7 SELECTING OPTIMAL MOTOR AND INVERTER CAPACITIES...
Страница 124: ...Part 5 Specifications Chapter 8 SPECIFICATIONS Chapter 9 FUNCTION CODES...
Страница 134: ...8 3 Common Specifications 8 9 Chap 8 SPECIFICATIONS 8 3 Common Specifications...
Страница 135: ...8 10...
Страница 257: ...App H Replacement Information A 33 App FVR C11S vs FRENIC Mini...
Страница 261: ...Glossary This glossary explains the technical terms that are frequently used in this manual...