3-8
3.3 Programming Mode
Pressing the
key in Running mode switches the inverter to Programming mode. This mode
provides the following functions which can be easily selected with the menu-driven system.
(1)
Data setting
(Menu #1)
(2)
Data checking
(Menu #2)
(3)
Drive monitoring
(Menu #3)
(4)
I/O checking
(Menu #4)
(5)
Maintenance information (Menu #5)
(6)
Alarm information
(Menu #6)
(7)
Data copying
(Menu #7)
The table below lists the menus, letters that will appear on the LED monitor, and functions. The
leftmost digit (numerals) of each letter string indicates the corresponding menu number and the
remaining three digits indicate the menu contents.
When the inverter enters Programming mode from the second time on, the menu that was selected
last in Programming mode will be displayed.
Table 3.3 Menus Available in Programming Mode
Menu
LED monitor
shows:
Main functions
Refer to:
1.F_ _
F codes (Fundamental functions)
1.E_ _
E codes
(Extension terminal functions)
1.C_ _
C codes
(Control functions of frequency)
1.P_ _
P codes (Motor parameters)
1.H_ _
H codes
(High performance functions)
1.J_ _
J codes (Application functions)
Menu #1
"Data setting"
1.y_ _
y codes (Link functions)
Selecting
each of these
function
codes enables
its data to be
displayed/
changed.
Section
3.3.1
Menu #2
"Data checking"
2. EP
Displays only function codes that have been
changed from their factory defaults. You may refer
to or change those function codes data.
Section
3.3.2
Menu #3
"Drive
monitoring"
3.oPE
Displays the running information required for
maintenance or test running.
Section
3.3.3
Menu #4
"I/O checking"
4. _o
Displays external interface information.
Section
3.3.4
Menu #5
"Maintenance
information"
5.CHE
Displays maintenance information including
cumulative running time.
Section
3.3.5
Menu #6
"Alarm
information"
6.AL
Displays the latest four alarm codes. You may
refer to the running information at the time when
the alarm occurred.
Section
3.3.6
Menu #7
"Data copying"
7.CPy
Allows you to read or write function code data, as
well as verifying it.
NOTE: To use this function, a remote keypad
(option) is necessary.
Содержание frenic mini series
Страница 1: ...USER S MANUAL Fuji Electric Co Ltd MEH446...
Страница 2: ...Compact Inverter User s Manual...
Страница 60: ...4 2 4 2 Drive Frequency Command Generator Figure 4 1 Block Diagram for Drive Frequency Command Generator...
Страница 62: ...4 4 4 3 Drive Command Generator Figure 4 2 Drive Command Generator...
Страница 66: ...4 8 Figure 4 3 d Terminal Command Decoder ORing with Link Commands Ignoring Link Commands...
Страница 68: ...4 10 4 5 Digital Output Selector Figure 4 4 Digital Output Signal Selector...
Страница 70: ...4 12 4 6 Analog Output FMA Selector Figure 4 5 Analog Output FMA Selector...
Страница 72: ...4 14 4 7 Drive Command Controller Figure 4 6 Drive Command Controller and Related Part of the Inverter...
Страница 74: ...4 16 4 8 PID Frequency Command Generator Figure 4 7 PID Frequency Command Generator...
Страница 81: ...Part 3 Peripheral Equipment and Options Chapter 6 SELECTING PERIPHERAL EQUIPMENT...
Страница 109: ...Part 4 Selecting Optimal Inverter Model Chapter 7 SELECTING OPTIMAL MOTOR AND INVERTER CAPACITIES...
Страница 124: ...Part 5 Specifications Chapter 8 SPECIFICATIONS Chapter 9 FUNCTION CODES...
Страница 134: ...8 3 Common Specifications 8 9 Chap 8 SPECIFICATIONS 8 3 Common Specifications...
Страница 135: ...8 10...
Страница 257: ...App H Replacement Information A 33 App FVR C11S vs FRENIC Mini...
Страница 261: ...Glossary This glossary explains the technical terms that are frequently used in this manual...