4.5.15 Installing the stoker unit
❒ Remove the pre-installed adjustable foot
❒ Turn round the adjustable foot and remount it
➥ Do not fasten the screwing yet
❒ Place the stoker unit at the plug-in flange and lay in the ceramic fibre seal
❒ Screw it with each 4 hexagonal bolts M10x35, washers M10 and hexagonal nuts
M10 to the plug-in flange
❒ Tighten the entire stoker unit incl. adjustable foot and fasten the screwing at the
adjustable foot
❒ Wrap the heat insulation mat around the stoker channel and fix the tension spring
❒ Hook the lower cover plate with the adapter onto the insulating side panel
Assembly
4
Mounting steps
Installation Instructions TX 150-250 | M1320112_en