4.5.2 Screwing the fire box with the heat exchanger
Positioning of the fire box from the side
❒ Insert the lift truck at the fire box opposite and lift it up as far as the fire box can be
positioned without colliding with the heat exchanger
❒ Bring in the fire box completely at the side of the heat exchanger and lower it slow‐
ly
❒ Remove the supporting post on the ash flange of the fire box
Positioning the fire box from the front
If there is not enough space to bring in the fire box from the side, it is possible to bring
it in from the front:
❒ Insert the lift truck at the fire box opposite the supporting post
❒ Place a piece of pipe, square timber or similar with a height of approx. 75 mm be‐
low the fire box as a distance piece
❒ Lift the fire box with the lifting truck and remove the supporting post on the ash
flange
❒ Position the loading arm of the lift truck by the openings of the main frame und in‐
sert the fire box as far as the distance piece can be positioned within the apron
❒ Lower the fire box, position the distance piece within the apron, lift the fire box
once again and bring it completely in.