2.4.6 Use with storage tank
NOTICE
In principle it is not necessary to use a storage tank for the system to run smooth‐
ly. However we recommend that you use the system with a storage tank, as this
ensures a continuous supply of fuel in the ideal output range of the boiler.
For the correct dimensions of the storage tank and the line insulation (in accordance
with ÖNORM M 7510 or guideline UZ37) please consult your installer or Froling.
2.4.7 Chimney connection/chimney system
EN 303-5 specifies that the entire flue gas system must be designed to prevent, wher‐
ever possible, damage caused by seepage, insufficient feed pressure and condensa‐
tion. Please note in this respect that flue gas temperatures lower than 160K above
room temperature can occur in the permitted operating range of the boiler.
The flue gas temperatures (for clean systems) and additional flue gas values can be
found in the table below.
The connection between the boiler and the chimney system should be as short as
possible. The upward angle of the connection should not exceed 30 - 45°. Insulate the
connection. The entire flue gas system - chimney and connection - should be calcula‐
ted in accordance with EN 13384-1.
Local regulations and other statutory regulations also apply.
NOTICE! The chimney must be authorised by a smoke trap sweeper or chimney
sweep.
NOTICE! TRVB H 118 (Austria only) stipulates that an explosion flap must be installed
in the connecting piece (flue pipe) directly next to the boiler. It should be situated in
such a way that is poses no risk to persons!
Draught limiter
The installation of a draught limiter is recommended.
NOTICE! Install the draught limiter directly under the mouth of the flue line, as the
pressure is constantly low at this point.