CS1012
Module for use as an M-Bus master. Heat meters approved by Froling can be read out on the M-Bus.
LED
Colour
Status
Description
r
Green
Off
Not in operation (no power supply)
Single Flash
Unlink mode
Double flash
Boot mode (during firmware update)
Flashing
Preoperative mode
On
Module in operation
e
Red
Off
No error / no supply to module
On
Error or reset status
e+r
Red illuminated (e)
Green flashing (r)
Incorrect firmware
S
Yellow
Off
None of the slaves send data
On
At least one slave transmits data via the M-Bus
P
Red
Off
M-Bus supply OK
On
Short circuit / overload on the M-Bus
Electric components and wiring
7
PLC
Service manual SPS 4000 | B0960622_en
103
Содержание SPS 4000
Страница 114: ...7 Electric components and wiring PLC 114 Fröling GesmbH A 4710 Grieskirchen Industriestraße 12 www froeling com ...
Страница 142: ...8 Notes 8 Notes 142 Fröling GesmbH A 4710 Grieskirchen Industriestraße 12 www froeling com ...