LED icon Status
Operating state
POWER:
ALARM:
GFI:
Alert or Alarm indication
• Indicates that the inverter control system has detected an alert or alarm. It is possible to identify the type of
problem generated in the dedicated section of integrated Web User Interface (“Event” section).
• Indicates missing of connections in case of external meter.
POWER:
ALARM:
GFI:
Temperature protection trip
Indicates that the trip relating to internal temperatures (insufficient or excessive temperature) may have been
activated.
POWER:
ALARM:
GFI:
Ventilation anomaly
Indicates ananomaly in the operation of the internal ventilation system that could limit output power at high
ambient temperatures.
Overvoltage surge arresters triggered (where fitted)
Indicates that any class II overvoltage surge arresters installed on the AC or DC side have been triggered
Internal statistics memory anomaly
Indicates an operating anomaly in the internal memory on which the inverter statistics are stored
Buffer battery discharged
The buffer battery is low and the inverter does not maintain the time setting
Autotest (for Italian grid standards only)
The inverter is performing an Autotest
POWER:
ALARM:
GFI:
Pre-commissioning phase (first start-up of inverter)
The commissioning of the inverter must be completed through the Installation wizard steps (Web User
Interface) or using the FIMER Installer for Solar Inverters mobile APP
Initial configuration failure
The inverter is in locked state due to a failure in the initial configuration of the equipment, such as the standard
network setting for the country of installation
Autotest not carried out (for Italian grid standards only)
Autotest operation failure
Incompatibility of the device firmware versions
The firmware versions of the various devices comprising the equipment are incompatible and are being updated
(this is an automatic operation)
Temperature sensor anomaly detected
POWER:
ALARM:
GFI:
Remote OFF activated
The Remote Off command has been activated.
The unit will not connect to the network until the remote ON command has been activated
POWER:
ALARM:
GFI:
Anomaly in the insulation system of the photovoltaic generator
Indicates that a leakage to earth from the PV generator has been detected, causing the inverter to disconnect
from the grid.
POWER:
ALARM:
GFI:
Arc fault Trip
During the reset procedure, the LED becomes fixed for 10 seconds. After this time, the LED switch OFF (which
means reset done) or start to blink again.
POWER:
ALARM:
GFI:
PID recovery function is active
Inverter is providing PID recovery functionality.
POWER:
ALARM:
GFI:
PID recovery function is enabled but not active
Inverter is not providing PID recovery functionality also if it is enabled. More detail on Web UI and Installer for
Solar Inverters App.
The following table shows all the possible status of “WLAN/LAN” LED on the Synoptic
(03)
according to the operating status of the Wi-Fi
or ethernet communication lines.
Led icon Status
Operating state
WLAN/LAN:
Wi-Fi not configured or/and ethernet cable not connected.
WLAN/LAN:
Scanning for available Wi-Fi networks.
WLAN/LAN:
Trying to reconnect to the Wi-Fi network
(after pressing the smart button for 5 seconds).
WLAN/LAN:
Wi-Fi or ethernet network is connected to the inverter and IP address is obtained.