5.4.6 Connection of AC output cable on AC
quick fit connector
ATTENTION –
A
The installation must be performed by
qualified installers and/or licensed electricians in accordance
with the existing regulations in the country of installation and
in accordance of all safety rules for performing electrical
works. The customer has civil liability for the qualification and
mental or physical state of the personnel who interact with
the equipment. They must always use the personal protective
equipment (PPE) required by the laws of the country of
destination and whatever is provided by their employer.
ATTENTION –
A
Before carrying out any operation, check
that any external AC switch downstream to the inverter (grid
side) is in OFF position applying LOTO procedure on it.
The connection of the AC cable must be made on the AC output
connector
(17)
, located on the bottom side of the inverter, using the
AC quick fit connector
(09)
.
• Unscrew the AC cable gland
(23)
installed on the AC quick fit
connector
(09)
.
• Remove the internal screw terminal block.
Press the 2 retain clips and pull out the screw terminal block.
19-26m
m
11-19m
m
19-26m
m
11-19m
m
19-2
6m
m
11-1
9m
m
19-2
6m
m
11-1
9m
m
ATTENTION –
A
On the connector cable gland 2 gasket
are installed that can be used in combination to accept a
11...26mm diameter cable.
- Cable diameter 11...19mm. Default configuration (both
gasket installed).
- Cable diameter 19...26mm. Remove the reducing clamping
range gasket.
• Pass the AC cable through the AC cable gland
(23).
• Strip the AC cable and wires
X
X
Y
12...16 mm
0.47...0.63 ”
Y
75...80 mm
2.95...3.15 ”
• Based on the AC connection type could be possible 4 scenarious:
A. Five-cores cable (L1, L2, L3, N and PE).
NOTE –
D
In this configuration the two PE cables must have
the same cross section of the phase cables.
B. Four-cores cable (L1, L2, L3 and N).
C. Four-cores cable (L1, L2, L3 and PE).
NOTE –
D
In this configuration the two PE cables must have
the same cross section of the phase cables.
D. Three-cores cable (L1, L2, L3).
L1 N PE
L2
L3
L1 N PE
L2
L3
L1 N PE
L2
L3
L1 N PE
L2
L3
L1 N PE
L2
L3
L1 N PE
L2
L3
L1 N PE
L2
L3
L1 N PE
L2
L3
A
C
B
D
• Install ferrule with plastic collar on the wires.
WARNING –
B
Ensure that the exposed wire core is totally
inserted into the terminal.