A. Technical appendix
Festo GDCC-CECX-K-D1-EN en 0802a
79
Property
Description
Maximum permissible continuous load (without
damage)
+/- 30 V
Indication of an overload
No indication on the card
Type of input
Differential
Sampling duration (incl. settling time)
1 ms
Sampling repeat time
1 ms
Input filter characteristics
Of the first order with 250 Hz transition frequency
Conversion methods
Successive approximation
Operation modes
Trigger
Safety device (RC, optocoupler, etc.)
Polyfuse
Common points between the channels
Reference potential: common GND for all inputs
Calibration or rechecking to maintain the accuracy
class
Calibration once during production
Consequence if the input terminals are connected
incorrectly
No consequences
Monotonity without fault codes
Yes
Non-linearity
≤ +/- 1 LSB
Table A.12 Analogue inputs