A.1.6
Output module CECX-D-14A-2
Type
CECX-D-14A-2
Product weight
[g]
135
Electrical connection technology for I/O
Socket strips with grid dimension 5.08 mm
Digital outputs
−
Number
−
Contact
−
Output voltage
−
Output current
−
Electrical isolation
−
Electrical isolation in groups
−
Short circuit proof
−
Status display
[V DC]
[A]
14
1)
Transistor
24
2 A with 50 % concurrence per group
2)
Yes, via optocoupler
Yes, in 2 groups
Yes
LED
1) Number in the GFDM diagnostic module dependent on the version status
2) 2 A per output; output current of group 1: max. 8 A; output current of group 2: max. 6 A
Table A.6 Periphery module CECX-D-14A-2
A.1.7
Input/output module CECX-A-4E4A-A
Type
CECX-A-4E4A-A
Product weight
[g]
135
Electrical connection technology for I/O
Socket strips with grid dimension 5.08 mm
Analogue inputs
−
Number
−
Resolution
−
Signal range
−
Value of the least significant bit (LSB)
−
Absolute accuracy at 25 °C
−
Electrical isolation
−
Input resistance
−
Sampling repeat time
[bit]
[mA]
[µA]
[%]
[
Ω]
[
ms]
4
1)
14
0 - 20, 4 - 20
1.35
±0.01
No
< 200
1
Analogue outputs
n. c. (reserved for extension)
1) Number in the GFDM diagnostic module dependent on the version status
Table A.7 Periphery module CECX-A-4E4A-A