Connections can be made in one of two ways:
•
By looping the RIO cable from terminal to
terminal. Both plugs are required here.
•
By connecting the RIO cable with a T-adapter.
Only one plug is required here.
CAUTION
Branches (e. g. T-adapter) can cause signal
reflections if high baud rates are used. This
leads to transmission errors and to brief failure
of the valves.
Recommendation
–
Do not exceed the maximum permitted
distance of 15 cm between the T-adapter
and the plug. In this way signal reflections
can be avoided.
–
Use the Festo T-adapter FB-TA for this
purpose.
Incoming
RIO
Continuing
RIO
Bild 3/16: Connecting variants for RIO network
Incoming
RIO
Cover with
protective cap
(IP 65)
Continuing
RIO
T-Adapter,
e.g. Festo
FB-TA
Branch
line max.
15 cm
VIFB8 - 03/05
3. Installation
3-30
9809c
Содержание 03-FB-8 Series
Страница 15: ...VIFB8 03 05 General safety instructions XIV 9809c ...
Страница 16: ...1 SYSTEM SUMMARY VIFB8 03 05 1 System summary 9809c 1 1 ...
Страница 28: ...2 FITTING VIFB8 03 05 2 Fitting 9809c 2 1 ...
Страница 41: ...3 INSTALLATION VIFB8 03 05 3 Installation 9809c 3 1 ...
Страница 74: ...4 COMMISSIONING VIFB8 03 05 4 Commissioning 9809c 4 1 ...
Страница 96: ...5 DIAGNOSIS AND ERROR TREATMENT VIFB8 03 05 5 Diagnosis and error treatment 9809c 5 1 ...
Страница 110: ...TECHNICAL APPENDIX VIFB8 03 05 Appendix A 9809c A 1 ...
Страница 122: ...INDEX VIFB8 03 05 Appendix B 9809c B 1 ...
Страница 126: ...V Valves 1 5 Voltage Cable selection 3 4 3 17 3 24 Connecting 3 15 3 19 3 22 3 26 3 29 VIFB8 03 05 Appendix B 9809c B 5 ...
Страница 127: ...VIFB8 03 05 Appendix B B 6 9809c ...