Possible RIO addresses
PLEASE NOTE
Set the address selector switches according to
the tables in Chapter 4, "Commissioning".
The following table shows the address range
with I/O racks of the relevant Allen-Bradley
controller.
Proceed as follows:
1. Switch off the power supply.
2. Assign a non-reserved RIO address to the
valve terminal.
3. Use a screwdriver to set the arrow of the rele-
vant address selector switch to the units or
tens figure of the desired RIO address.
A-B programmable
controller family
Possible range of
I/O rack no.
PLC-2
2; ...; 7
PLC-3
1; ...; 30
PLC-5/250
1; ...; 17
PLC-5/15
01; ...; 03
PLC-5/25
01; ...; 07
PLC-5/30
01; 02; ...; 07
PLC-5/40;
PLC-5/60
01; ...; 27
SLC-5/02 with 1747-SN
0; ...; 3
Fig. 3/5: RIO addresses
VIFB8 - 03/05
3. Installation
3-12
9809c
Содержание 03-FB-8 Series
Страница 15: ...VIFB8 03 05 General safety instructions XIV 9809c ...
Страница 16: ...1 SYSTEM SUMMARY VIFB8 03 05 1 System summary 9809c 1 1 ...
Страница 28: ...2 FITTING VIFB8 03 05 2 Fitting 9809c 2 1 ...
Страница 41: ...3 INSTALLATION VIFB8 03 05 3 Installation 9809c 3 1 ...
Страница 74: ...4 COMMISSIONING VIFB8 03 05 4 Commissioning 9809c 4 1 ...
Страница 96: ...5 DIAGNOSIS AND ERROR TREATMENT VIFB8 03 05 5 Diagnosis and error treatment 9809c 5 1 ...
Страница 110: ...TECHNICAL APPENDIX VIFB8 03 05 Appendix A 9809c A 1 ...
Страница 122: ...INDEX VIFB8 03 05 Appendix B 9809c B 1 ...
Страница 126: ...V Valves 1 5 Voltage Cable selection 3 4 3 17 3 24 Connecting 3 15 3 19 3 22 3 26 3 29 VIFB8 03 05 Appendix B 9809c B 5 ...
Страница 127: ...VIFB8 03 05 Appendix B B 6 9809c ...