Address assignment after extension/
conversion
A special feature of the modular valve terminal is
its flexibility. If the demands placed on the
machine change, then the equipment fitted on the
terminal can also be modified.
CAUTION
If extensions or conversions are made to the
terminal at a later stage, this may result in a
shifting of the input/output addresses. This
applies in each of the following cases:
•
If one or more pneumatic modules is/are
fitted/removed at a later stage (type 03).
•
If a pneumatic module with single valves is
replaced by a module with double valves or
vice versa (type 03).
•
If additional input/output modules are inser-
ted between the node and existinginput/
output modules.
•
If existing 4-input modules are replaced
by 8-input modules or vice versa.
If the configuration is changed from a quarter rack
to a half rack, the addresses of the status bits will
be shifted.
VIFB8 - 03/05
4. Commissioning
4-14
9809c
Содержание 03-FB-8 Series
Страница 15: ...VIFB8 03 05 General safety instructions XIV 9809c ...
Страница 16: ...1 SYSTEM SUMMARY VIFB8 03 05 1 System summary 9809c 1 1 ...
Страница 28: ...2 FITTING VIFB8 03 05 2 Fitting 9809c 2 1 ...
Страница 41: ...3 INSTALLATION VIFB8 03 05 3 Installation 9809c 3 1 ...
Страница 74: ...4 COMMISSIONING VIFB8 03 05 4 Commissioning 9809c 4 1 ...
Страница 96: ...5 DIAGNOSIS AND ERROR TREATMENT VIFB8 03 05 5 Diagnosis and error treatment 9809c 5 1 ...
Страница 110: ...TECHNICAL APPENDIX VIFB8 03 05 Appendix A 9809c A 1 ...
Страница 122: ...INDEX VIFB8 03 05 Appendix B 9809c B 1 ...
Страница 126: ...V Valves 1 5 Voltage Cable selection 3 4 3 17 3 24 Connecting 3 15 3 19 3 22 3 26 3 29 VIFB8 03 05 Appendix B 9809c B 5 ...
Страница 127: ...VIFB8 03 05 Appendix B B 6 9809c ...