There is a yellow LED for each pilot solenoid coil.
This LED shows the switching status of the pilot
solenoid coil.
12 14 12
14 12 14
12
14
Yellow LEDs
LED
Switch position
of pilot coil
Meaning
Yellow off
Basic position
Logic 0 (no signal)
Yellow on
•
Switch position
or
•
basic position
Logic 1 (signal applied)
Logic 1 but:
•
Operating voltage of outputs is
below permitted tolerance range
(DC 21.6 V...26.4 V)
or
•
compressed air supply not correct
or
•
pilot exhaust blocked
or
•
call servicing personnel
Fig. 5/5: LED display – switching status of ISO pilot solenoid coil
VIFB8 - 03/05 5. Diagnosis and error treatment
9809c
5-7