General information (types 03 and 05)
PLEASE NOTE
When configured in an RIO network, the valve
terminal occupies 32 (quarter rack) or 64 (half
rack) input and output addresses.
Unused input and/or output addresses must
be left free and must not be used for other
modules.
The address assignment of the outputs of a
modular valve terminal depends on the equipment
fitted on the terminal. A distinction must be made
between the following equipment fitted:
•
valves and digital I/O modules
•
valves only
•
digital I/O modules only.
The basic rules described below apply to the
address assignment of this equipment.
PLEASE NOTE
If one valve location occupies two addresses
the addresses are assigned as follows:
•
lower address
⇒
pilot solenoid coil 14
•
higher address
⇒
pilot solenoid coil 12
VIFB8 - 03/05
4. Commissioning
9809c
4-9