3.2.1 Type 03:
Connecting the operating voltages
WARNING
Use only power units which guarantee reliable
isolation of the operating voltages as per IEC
742/EN 60742/VDE 0551 with at least 4 kV
isolation resistance (protected extra low volt-
age, PELV). Switch power packs are permitted
if they guarantee reliable isolation in accord-
ance with EN 60950/VDE 0805.
Remark:
Protection against electric shock (protection
against direct and indirect contact) is guaranteed
on Festo valve terminals by the use of PELV
power units in accordance with EN 60204-1/IEC
204. The valve terminals must be earthed in order
to ensure their function (e.g. EMC).
CAUTION
The power supply to the outputs/valves (pin 2)
must be separately fused externally with max.
10 A. The external fuse prevents the valve ter-
minal from being damaged in the event of a
short circuit.
VIFB8 - 03/05
3. Installation
9809c
3-15
Содержание 03-FB-8 Series
Страница 15: ...VIFB8 03 05 General safety instructions XIV 9809c ...
Страница 16: ...1 SYSTEM SUMMARY VIFB8 03 05 1 System summary 9809c 1 1 ...
Страница 28: ...2 FITTING VIFB8 03 05 2 Fitting 9809c 2 1 ...
Страница 41: ...3 INSTALLATION VIFB8 03 05 3 Installation 9809c 3 1 ...
Страница 74: ...4 COMMISSIONING VIFB8 03 05 4 Commissioning 9809c 4 1 ...
Страница 96: ...5 DIAGNOSIS AND ERROR TREATMENT VIFB8 03 05 5 Diagnosis and error treatment 9809c 5 1 ...
Страница 110: ...TECHNICAL APPENDIX VIFB8 03 05 Appendix A 9809c A 1 ...
Страница 122: ...INDEX VIFB8 03 05 Appendix B 9809c B 1 ...
Страница 126: ...V Valves 1 5 Voltage Cable selection 3 4 3 17 3 24 Connecting 3 15 3 19 3 22 3 26 3 29 VIFB8 03 05 Appendix B 9809c B 5 ...
Страница 127: ...VIFB8 03 05 Appendix B B 6 9809c ...