2.2 TYPE 03: FITTING THE VALVE TERMINAL
Wall fitting (type 03)
WARNING
With long terminals (e.g. several I/O modules)
use additional supporting brackets every
200 mm. You can then avoid:
•
overloading the fastening eyes on the
left-hand end plate
•
the terminal sagging
•
natural resonances
Proceed as follows:
•
Calculate the weight of the terminal (weigh or
estimate). General rule:
•
Make sure that the fastening surface can
carry this weight.
•
Fasten the terminal with four M6 screws as
shown below (fitting position as desired). Use
washers if necessary.
7.6 mm
M6
Fig. 2/4: Wall fitting – type 03
MIDI
MAXI
per pneumatic module
800 g
1200 g
per node
1000 g
1000 g
per electric module
400 g
400 g
VIFB8 - 03/05
2. Fitting
9809c
2-9