FIRE - FIRE zones on the system contain Fire Verification Logic. Upon detection of the first
violation, smoke detector power will be reset for a period of 8 seconds. After this time period,
power is restored. For a period of 5 seconds the fire zone will not be scanned allowing the
smoke detectors to settle. Future violations within a two-minute period will result in a
PULSING BELL OUTPUT, RAPID PULSING ZONE LED, and IMMEDIATE transmission
to the CS. Fire signals cannot be aborted.
Entry of any valid user code will silence the sounder, bell and reset smoke detector power. If
the system detects that the fire zone is still violated within 2 minutes of power reset, the
zone LED will pulse slowly to indicate a fire trouble. Thereafter, smoke detector power will
be reset every 4 minutes automatically in an attempt to clear the fire zone.
In the event the fire zone experiences an open, the system indicates fire trouble by pulsing
the keypad zone LED and sounder slowly. The system trouble code (followed by the zone
code) will be reported to the CS.
The keypad sounder can be SILENCED through entry of ANY VALID USER CODE. NOTE:
FIRE ZONES cannot be bypassed. ZONE 4 CAN BE PROGRAMMED AS A FIRE ZONE
FOR BELL SUPERVISION.
24 HR. ALARM - This zone type is always active, independent of the system arming status.
Programming options include audible (STEADY BELL) or silent (NO BELL or keypad
indications). Upon violation the zone LEDs will pulse rapidly (audible zones only) and an
immediate CS transmission will occur which cannot be aborted.
24 Hour Alarm zones can be bypassed, however they cannot be unbypassed if a violation
exists on the zone terminals.
24 HR. TROUBLE - This zone type is always active, independent of the system arming
status. Programming options include audible (PULSING KEYPAD SOUNDER) or silent.
Upon violation the zone LED will pulse slowly. Trouble condition must exist for 15 seconds
before a transmission will occur. The keypad display and sounder will clear upon zone
restoral.
24 Hour Trouble zones can be bypassed, however they cannot be unbypassed if a violation
exists on the zone terminals.
24-hour trouble is not to be used for fire and burglary detection zones. 24-Hour silent alarm zones
are not to be used for perimeter protection. THE SOUNDER MAY BE SILENCED THROUGH
ENTRY OF ANY VALID USER CODE.
WARNING: Fire Zones CANNOT BE BYPASSED. 24 Hour zones CAN BE
BYPASSED, however, they CANNOT BE UNBYPASSED if a violation exists on their
terminals.
Zone Alarm Codes
As previously specified locations L3 and L4 of the zone questions represent the alarm code
that will be reported to the central station.
Zones will transmit to the Central Station unless these digits are defined as AA for any individual
zone, or the local dialer option is selected for all zones in question #04, location 1.
Based on the dialer format selected enter the alarm code as follows:
STANDARD FORMAT (3X1 or 4X1): Enter the desired single digit alarm code in location
L3 for the specific zone. The value placed in L4 will not be used.
Содержание XL-1S
Страница 8: ...viii ...
Страница 10: ...XL 1S Hookup and Installation Instructions 1 2 ...
Страница 18: ...XL 1S Hookup and Installation Instructions 2 8 ...
Страница 26: ...XL 1S Hookup and Installation Instructions 5 4 ...
Страница 34: ...XL 1S Hookup and Installation Instructions 7 4 ...
Страница 53: ...XL 1S Hookup and Installation Instructions 9 4 ...
Страница 55: ...XL 1S Hookup and Installation Instructions 10 2 ...
Страница 57: ...XL 1S Hookup and Installation Instructions 11 2 ...
Страница 61: ...XL 1S Hookup and Installation Instructions B 2 ...
Страница 63: ...XL 1S Hookup and Installation Instructions C 2 ...
Страница 65: ...XL 1S Hookup and Installation Instructions D 2 ...
Страница 69: ...XL 1S Hookup and Installation Instructions F 2 ...
Страница 71: ... 1 9 l N9471V1 06 98 Copyright 1998 PITTWAY CORPORATION ...