XL-1S Hookup and Installation Instructions
2–2
Terminal Connections
TERMINALS
DESCRIPTION
1(+) & 2(-)
Zone 1 (Requires 2.2K EOL resistor)
[Default = DELAY]
3(+) & 2(-)
Zone 2 (Requires 2.2K EOL resistor)
[Default = INTERIOR]
4(+) & 5(-)
Zone 3 (Requires 2.2K EOL resistor)
[Default = PERIMETER]
6(+) & 5(-)
Zone 4 (Requires 2.2K EOL resistor)
[Default = PERIMETER]
ZONE INFORMATION:
Normally closed devices may be wired in series and/or normally open
devices in parallel with the 2.2k ohm end of line resistor on all zones
(Refer to the wiring diagram). The standard loop response time is 280 ms
on all zones. Each zone can be programmed for Fast Response (10 ms)
in programming (see questions #10-13). The factory default values for
each zone is listed in the table above, however any zone can be
programmed for the following types: Delay, Perimeter, Interior, Fire, 24
Hr. Alarm, or 24 Hr. Trouble. Further explanation of the zone types can
be found in the System Programming section of this manual.
NOTE: Loop response is defined as the minimum time required for a
fault to trip a zone.
5 & 7
PANIC CIRCUIT OR KEYSWITCH:
Normally Open PANIC circuit. This hardwired panic is a 24-hour zone
that can be programmed for silent or audible operation. The panic circuit
will activate with each violation, therefore a latched device is not
recommended. A momentary device is recommended. For UL
installations, the panic switch connected to these terminals is to be
located no more than 3 feet from the control unit, with no intervening
barriers (this is a supervision requirement only). If the keyswitch option
is selected (see programming question #05, location 2), then each
activation of the keyswitch will arm and disarm the system.
NOTE: EOL resistor is not required on this zone and is not supervised.
This zone does not report restore codes. If a supervised zone with restore
reporting ability is desired, then program one of the 4 ZONES as a 24Hr.
Alarm. If used as a keyswitch, then triggers are available for either an
arming or ready status indication (see programming question #07,
location 4).
8
EARTH GROUND:
Connect this grounding lug to a cold water pipe utilizing #18AWG wire at
a distance of no greater than 15 ft. Use a non-corrosive metal strap firmly
secured to the pipe to which the lead is electrically connected and
secured. If the premises pipes terminate in PVC, this terminal must be
connected to a six- (6) foot grounding rod.
9 10 11 12
KEYPADS:
A maximum of 4 keypads, either XK-104 or 6805, may be wired to these
terminals. The connections are as follows; 9 (BLACK = negative), 10
(YELLOW = data in), 11 (GREEN = data out) and 12 (RED = positive
power). Each keypad draws approximately 30mA. Maximum keypad
length is 500 feet using 22-gauge wire. NOTE: In some installations, it
may be necessary to use shielded wire to prevent radio frequency
interference.
Содержание XL-1S
Страница 8: ...viii ...
Страница 10: ...XL 1S Hookup and Installation Instructions 1 2 ...
Страница 18: ...XL 1S Hookup and Installation Instructions 2 8 ...
Страница 26: ...XL 1S Hookup and Installation Instructions 5 4 ...
Страница 34: ...XL 1S Hookup and Installation Instructions 7 4 ...
Страница 53: ...XL 1S Hookup and Installation Instructions 9 4 ...
Страница 55: ...XL 1S Hookup and Installation Instructions 10 2 ...
Страница 57: ...XL 1S Hookup and Installation Instructions 11 2 ...
Страница 61: ...XL 1S Hookup and Installation Instructions B 2 ...
Страница 63: ...XL 1S Hookup and Installation Instructions C 2 ...
Страница 65: ...XL 1S Hookup and Installation Instructions D 2 ...
Страница 69: ...XL 1S Hookup and Installation Instructions F 2 ...
Страница 71: ... 1 9 l N9471V1 06 98 Copyright 1998 PITTWAY CORPORATION ...