![Fairford Electronics QFE Series Скачать руководство пользователя страница 84](http://html1.mh-extra.com/html/fairford-electronics/qfe-series/qfe-series_manual_3218507084.webp)
FD8416 5MC Bit Parameters
03 September 2003
55
55
55
55
Software
.
11
11
11
11
STATUS 1
8
Bitmask
Name
Type
Default
= ON
Description
Parameter
Stopped
Status
start/stop signal inactive thyristors
off main contactor open
00000001
(
)
1
Starting
Status
Starter is in start ramp
00000010
(
)
2
Current Limit
Status
During a softstart indicates motor
has reached Current limit level and
ramp is being held.
00000100
(
)
4
Top Of Ramp
Status
The unit has finished the start ramp
and any current limit
00001000
(
)
8
Dwell
Status
Period of timre at the the end of the
start ramp where the motor is held at
full volts before entering optimising
to allow the load to stabilise
00010000
(
)
16
Full Conduction
Status
Thyristors are fully on
00100000
(
)
32
Energy Saving
Status
Starter is monitoring the motor
power factor and adjusting applied
voltage to bring it close to optimum.
01000000
(
)
64
Stopping
Status
The starter is performing a stop ramp
10000000
(
)
128
STATUS 2
9
Bitmask
Name
Type
Default
= ON
Description
Parameter
Alarm
Status
Starter has detected a fault and has
tripped
00000001
(
)
1
Overload Integrating Status
The on board overload has detected
over current and is integrating
00000010
(
)
2
Stall
Status
The starter has detected that the
motor speed is slipping
00000100
(
)
4
Forced Override
Status
The starter has turned off optimising
since the current has risen above
80% FLC
00001000
(
)
8
Noise
Status
The starter is experiencing poor
mains reference signals
00010000
(
)
16
Inhibit Start
Status
The start is inhibited for a period to
keep the unit within its allowable
start duty.
00100000
(
)
32
DC I/p level reached Status
The DC I/p has risen above the level
specified in parameter 48
01000000
(
)
64
4-20mA level
reached
Status
The4-20mA I/p has risen above the
level specified in parameter 46
10000000
(
)
128
Page 1 of 8
Содержание QFE Series
Страница 17: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Mechanical Installation FD841205_F...
Страница 18: ...Mechanical Installation QFE page 1 2 FD841205_F...
Страница 26: ...Mechanical Installation QFE page 1 10 FD841205_F...
Страница 27: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Electrical Installation FD8413 issue03_F...
Страница 43: ...QFE page 2 19 Electrical Installation FD8413 issue03_F...
Страница 50: ...Electrical Installation QFE page 2 26 FD8413 issue03_F...
Страница 51: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Applications...
Страница 73: ...QFE page 3 25 Applications FD841405_F...
Страница 112: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Programming Guide FD8420 issue02_F...
Страница 158: ...page 5 47 Programming QFE FD8420 issue02_F This page is left intentionally blank...