FD8416 5MC Parameters
03 September 2003
55
55
55
55
Software
.
11
11
11
11
65
I/P1 MAP TO
52
125
0
prmtr
Read/Write
Value is parameter number which is the destination for the
I/p1 bit.
Parameter 66 holds the mask for mapping I/p1 into.
This is normally the start/stop I/p (remote).
It would be unusual for it to be anything else.
Description
Hints
PN
Parameter Name
Default
Max
Min
Units
Type
Scaling
1
Std
66
I/P1 BIT MASK
16
128
0
mask
Read/Write
Parameter 66 holds the mask for mapping I/p1 into.
Description
Hints
PN
Parameter Name
Default
Max
Min
Units
Type
Scaling
1
Std
67
I/P2 MAP TO
0
125
0
prmtr
Read/Write
Value is parameter number which is the destination for the
I/p2 bit.
Parameter 68 holds the mask for mapping I/p2 into.
Description
Hints
PN
Parameter Name
Default
Max
Min
Units
Type
Scaling
1
Std
68
I/P2 BIT MASK
0
128
0
mask
Read/Write
Parameter 68 holds the mask for mapping I/p2 into.
Description
Hints
PN
Parameter Name
Default
Max
Min
Units
Type
Scaling
1
Std
69
I/P3 MAP TO
0
125
0
prmtr
Read/Write
Value is parameter number which is the destination for the
I/p3 bit.
Parameter 70 holds the mask for mapping I/p3 into.
Description
Hints
PN
Parameter Name
Default
Max
Min
Units
Type
Scaling
1
Std
70
I/P3 BIT MAP
0
128
0
mask
Read/Write
Parameter 70 holds the mask for mapping I/p2 into.
Description
Hints
PN
Parameter Name
Default
Max
Min
Units
Type
Scaling
1
Std
71
CONTACTOR DELAY
160
800
20
mS
Read/Write
Following a start command this is the delay allowed for the
main incomming contactor to close. After this time a phase
loss detection routine checks for the incomming supply.
Description
Hints
PN
Parameter Name
Default
Max
Min
Units
Type
Scaling
4
Std
72
TRIP SENSITIVITY
1
15
1
none
Read/Write
An arbitrary number to adjust the sensitivity of some of the
fault trips. The larger the number the slower the trip.
Description
Hints
PN
Parameter Name
Default
Max
Min
Units
Type
Scaling
1
Std
Page 9 of 17
Содержание QFE Series
Страница 17: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Mechanical Installation FD841205_F...
Страница 18: ...Mechanical Installation QFE page 1 2 FD841205_F...
Страница 26: ...Mechanical Installation QFE page 1 10 FD841205_F...
Страница 27: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Electrical Installation FD8413 issue03_F...
Страница 43: ...QFE page 2 19 Electrical Installation FD8413 issue03_F...
Страница 50: ...Electrical Installation QFE page 2 26 FD8413 issue03_F...
Страница 51: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Applications...
Страница 73: ...QFE page 3 25 Applications FD841405_F...
Страница 112: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Programming Guide FD8420 issue02_F...
Страница 158: ...page 5 47 Programming QFE FD8420 issue02_F This page is left intentionally blank...
Страница 181: ...Modbus page 6 4 5MC FD510007...