Commissioning 2
If the softstart trips on overload during the start, check starter is large enough for the load.
No :
Date :
Subject :
24
02/09/2003
"Too Hot"
Check ventilation into the cabinet. If the unit has worked for a long time check fans and airflow
through unit.
No :
Date :
Subject :
Wiring
Category
2
24/06/2002
When replacing star delta starters
If you are planning to re use the existing overload and contactor, ensure they are sized for the full
motor line current and not just for delta phase current.
No :
Date :
Subject :
8
09/09/2002
Running inside the DELTA 1
The unit must be set to firing mode 1. The current displayed is now the phase current (58% of the
line current).
No :
Date :
Subject :
11
11/09/2002
Running inside the DELTA 2
When running with firing mode 1 the maximum cable length between the starter and the motor is
reduced to 50M.
No :
Date :
Subject :
14
02/09/2003
Running inside the DELTA 3
When running in the delta an inline contactor must be used.
No :
Date :
Subject :
03 September 2003
Page 3 of 3
Содержание QFE Series
Страница 17: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Mechanical Installation FD841205_F...
Страница 18: ...Mechanical Installation QFE page 1 2 FD841205_F...
Страница 26: ...Mechanical Installation QFE page 1 10 FD841205_F...
Страница 27: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Electrical Installation FD8413 issue03_F...
Страница 43: ...QFE page 2 19 Electrical Installation FD8413 issue03_F...
Страница 50: ...Electrical Installation QFE page 2 26 FD8413 issue03_F...
Страница 51: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Applications...
Страница 73: ...QFE page 3 25 Applications FD841405_F...
Страница 112: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Programming Guide FD8420 issue02_F...
Страница 158: ...page 5 47 Programming QFE FD8420 issue02_F This page is left intentionally blank...
Страница 181: ...Modbus page 6 4 5MC FD510007...