![Fairford Electronics QFE Series Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/fairford-electronics/qfe-series/qfe-series_manual_3218507015.webp)
all terminations
are for M12
151
621
635
200
200
175
56
193
102
61
193
60
138
ALL DIMENSIONS IN mm.
Minimum top/bottom clearance - 200mm
Minimum side clearance - 25mm
Minimum front clearance - 25mm
NOTE - LIVE HEATSINKS
Air
Flow
Mechanical Outline 1200 Amp “O” Range Soft Starter
FD85D602 M-85D6
Current Transformers
Due to the Current ratings of this size of Soft Starters, an “Interposing CT” is required. A small CT is fitted
internally to these units and an additional CT, rated for the size of the Starter, is provided separately. This
MUST be fitted onto the conductors in the L3-T3 phase and be connected to the marked terminal block
under the front cover.
Содержание QFE Series
Страница 17: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Mechanical Installation FD841205_F...
Страница 18: ...Mechanical Installation QFE page 1 2 FD841205_F...
Страница 26: ...Mechanical Installation QFE page 1 10 FD841205_F...
Страница 27: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Electrical Installation FD8413 issue03_F...
Страница 43: ...QFE page 2 19 Electrical Installation FD8413 issue03_F...
Страница 50: ...Electrical Installation QFE page 2 26 FD8413 issue03_F...
Страница 51: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Applications...
Страница 73: ...QFE page 3 25 Applications FD841405_F...
Страница 112: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Programming Guide FD8420 issue02_F...
Страница 158: ...page 5 47 Programming QFE FD8420 issue02_F This page is left intentionally blank...
Страница 181: ...Modbus page 6 4 5MC FD510007...