![Fairford Electronics QFE Series Скачать руководство пользователя страница 109](http://html1.mh-extra.com/html/fairford-electronics/qfe-series/qfe-series_manual_3218507109.webp)
Tech Hints
General
Category
3
10/07/2002
Motor configuration
If the motor starts ok but stalls as soon as a load is applied then check the configuration of the motor,
i.e it may be that the motor is meant to be connected in delta but is actually connected in star
No :
Date :
Subject :
4
23/08/2002
Thermistor(1)
Thermistors are non linear devices, An analog input has been used to monitor the thermistor, with
no thermistor connected the parameter will read 255, with a cold thermistor the value will be low or
zero but with an over temperature thermistor the value will be high or 255.
No :
Date :
Subject :
9
10/09/2002
Kick Start
Kick start is not always suitable for use with rolling starts or very light loads.
No :
Date :
Subject :
12
05/11/2002
Fuse Bodies
Smaller Fuse bodies can age worse with repeated starts.
No :
Date :
Subject :
15
02/09/2003
Modbus
From Software version 55.00 circuit board comms is by a subset of the modbus protocol.
No :
Date :
Subject :
16
02/09/2003
Enable and Disable
From Software version 55.00 enable and disable modes are introduced, the unit must be disabled to
save to permanent store etc.
No :
Date :
Subject :
17
02/09/2003
Slip ring motors 1
When sizing a single stage of resistors for use with a soft starter, care must be taken to balance the
standstill torque requirements against large slips at full volts.
No :
Date :
Subject :
18
02/09/2003
Slip ring motors 2
Slip rings may be shorted at part voltage by forcing a user current limit at start, then using the current
limit timeout flag to control K2 and hence the shorting contactor.
No :
Date :
Subject :
20
02/09/2003
Commissioning 1
It is a good idea to start by using one of the standard applications.
No :
Date :
Subject :
22
02/09/2003
Sizing Starters
Starters may need to be de-rated for high start frequency, current, ambient temperature, altitude or
long starts.
No :
Date :
Subject :
03 September 2003
Page 1 of 3
Содержание QFE Series
Страница 17: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Mechanical Installation FD841205_F...
Страница 18: ...Mechanical Installation QFE page 1 2 FD841205_F...
Страница 26: ...Mechanical Installation QFE page 1 10 FD841205_F...
Страница 27: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Electrical Installation FD8413 issue03_F...
Страница 43: ...QFE page 2 19 Electrical Installation FD8413 issue03_F...
Страница 50: ...Electrical Installation QFE page 2 26 FD8413 issue03_F...
Страница 51: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Applications...
Страница 73: ...QFE page 3 25 Applications FD841405_F...
Страница 112: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Programming Guide FD8420 issue02_F...
Страница 158: ...page 5 47 Programming QFE FD8420 issue02_F This page is left intentionally blank...
Страница 181: ...Modbus page 6 4 5MC FD510007...