![Fairford Electronics QFE Series Скачать руководство пользователя страница 134](http://html1.mh-extra.com/html/fairford-electronics/qfe-series/qfe-series_manual_3218507134.webp)
page 5-23
Programming
QFE
FD8420 issue02_F
5.3.11
The Trips Menu
This menu holds all the parameters that are associated with control of the various trips
Trips
-
This sub menu accesses a trip history of the unit’s last
five trips. These trips are recorded automatically and need no intervention from the user.
They are useful in fault-finding a unit.
Trip-1
-
This parameter records the trip number of the last
recorded trip.
Trip-2
-
This parameter records the trip number of the
second last recorded trip.
Trip-3
-
This parameter records the trip number of the third
last recorded trip.
Trip-4
-
This parameter records the trip number of the fourth
last recorded trip.
Trip-5
-
This parameter records the trip number of the fifth
last recorded trip.
Note that most trips can be turned off, either via this menu, or through the
Trip
Byte
,
P127
, or via the
Current
menu for the current related trips. Below is a list of
each trip condition used by the QFE. For each trip condition there is a small paragraph
in the form;
Trip No
Trip Name
Explanation
01
Phase Loss
If one or more supply phases is missing when the unit is running a load (see
Note
section
5.3.4
,
Line Contactor
).
02
Too Hot
Fan cooled units are fitted with an internal thermal switch. The unit will trip if it detects
an over temperature signal.
03
Comms
The unit will trip if communication fails between the user interface and the soft starter.
04 - 10
Thyristor Firing
These trips indicate that one or more of the thyristors is malfunctioning,
11
Low Current
The unit will trip if the unit’s output current falls below a previously set level (
P28
Low
Amps Level
) for a specified time (
P29
Low Amps Time
).
Содержание QFE Series
Страница 17: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Mechanical Installation FD841205_F...
Страница 18: ...Mechanical Installation QFE page 1 2 FD841205_F...
Страница 26: ...Mechanical Installation QFE page 1 10 FD841205_F...
Страница 27: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Electrical Installation FD8413 issue03_F...
Страница 43: ...QFE page 2 19 Electrical Installation FD8413 issue03_F...
Страница 50: ...Electrical Installation QFE page 2 26 FD8413 issue03_F...
Страница 51: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Applications...
Страница 73: ...QFE page 3 25 Applications FD841405_F...
Страница 112: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Programming Guide FD8420 issue02_F...
Страница 158: ...page 5 47 Programming QFE FD8420 issue02_F This page is left intentionally blank...
Страница 181: ...Modbus page 6 4 5MC FD510007...