Irideon Control Installation and User Manual
23
Remote Control Stations
Remote Control Stations which include Recall Stations, Closure Stations,
and Receptacle Stations reside on a single data run and are to be wired in
a daisy-chain configuration with a 120 ohm termination resistor between
the two data lines(+&-) after the last station. Recommended maximum
overall cable length
for the remote control run cannot exceed 1000 feet
total.
Step 1:
Mounting:
a. For 8-Button and Closure/Join stations use RACO #681
(4”square x 2-1/8”deep) double box or equivalent. All other
stations use RACO #680 single box (2-1/2” deep gang able)
or equivalent.
Step 2:
For installations not including the Irideon Astronomical Time
Clock, Data and DC power should be run from the MCP then
daisy chained from station to station.
a. For installations including the ATC, Data and DC Power
should be run from the MCP to the ATC, then daisy-chained
from the ATC to the next station. Continue the single run
daisy chain and install a 120 ohm termination resistor
between the two data lines (+ & -) after the last station.
Step 3:
Remove the remote station faceplate exposing a 2-position (DC
power) and a 3-position (Data) terminal strip and mounting
holes for attachment of station to the junction box. For those
stations with a hinged cover, screws behind the cover hold the
faceplate in place. For those stations without a hinged cover, a
screwdriver may be used to gently pry the faceplate loose from
the bottom of the station.
Step 4:
The terminal strips are of a two part plug-in style. Remove the
outer section to allow wire connection.Connect the data using
the following pin/wire code:
Step 5:
Connect the DC power using the following pin/wire code:
Step 6:
Reconnect the two part terminal strips.
Step 7:
Using a small screwdriver, set the two rotary switches to the
fixture address assigned to the remote station. This information
should come from the same source as the luminaire addresses.
N o t e :
Remote Stations should have a unique address number from other
Remote Stations in the system. Since Remote Station addresses are not
linked in any way to luminaire addresses you may assign address
numbers also assigned to luminaires without fear of complications.
Pin
Wire (Cat 5)
Belden 9729
data +
White/Orange
Red
data -
Orange
Black
Gnd
Brown
Drain
Pin
Wire Belden 8461
Wire (Belden 8790)
+ (24vdc)
Black
Red
Gnd
White
White
Содержание IRIDEON
Страница 10: ...6 Introduction This page intentionally blank...
Страница 44: ...40 System Test This page intentionally blank...
Страница 50: ...46 Troubleshooting This page intentionally blank...
Страница 60: ...56 Maintenance This page intentionally blank...
Страница 64: ...60 Software Hardware Components This page intentionally blank...
Страница 70: ...66 Astronomical Time Clock installation instructions This page intentionally blank...
Страница 83: ...Irideon Control Installation and User Manual 79 This page intentionally blank...