Irideon Control Installation and User Manual
17
Input Power and Control Cabling for Irideon
Control System
N o t e :
The following wiring requirements apply to Irideon products with the
exception of the Luminaire Programming Jack (LPJ) and the Keyswitch
(KS) station.
Data and AC power are to be routed through separate conduit. When
terminating data and AC power in a common junction box, wiring must be
separated by a dividing panel.
Data and DC power from MCP to Remote Stations may be routed through
the same conduit. Termination of data and DC power within the junction
box does not require isolation of power and data lines.
Signal Type
From Source To:
In Conduit
Without Conduit
Data
Luminaire
Belden 9729
Belden 89729
Data
Remote Stations
Belden 9729
Belden 89729
DC Power
Remote Stations
Belden 8461 or
2-#18 gauge
Not Recommended
AC Power
Luminaire
18-10 AWG
Not Recommended
AC Power
MCP / DMX Interpreter 18-10 AWG
Not Recommended