Technical data
9
The flue gas connection on the boiler does not yet give any indication of the required chimney diameter.
Information on the required chimney diameter can be found in the installation instructions for the boiler in the
Chimney chapter.
Subject to technical changes and errors
Pellet boiler
Unit
180
199
220
240
Rated capacity
kW
53.9 -
179.9
59.9 -
199.9
65.9 -
219.9
71.9 -
239.9
Efficiency at partial / full load
%
94.3 / 94.4 95 / 94.9 95.7 / 95.3 96.5 / 95.8
Transport dimensions (boiler) W x D x H
mm
1076 x 2073 x 1970
Transport dimensions (pellet module) W x D x H
mm
1130 x 650 x 2124
Weight of the boiler
kg
1982
Weight of the pellet module
kg
200
Water content
litres
434
Water-side pressure drop (ΔT = 20 K)
mWs
0.83
1.03
1.24
1.46
Available residual pump head (at ΔT = 20 K) for buffer
operation
mWs
6.5
5.5
4
2.5
m³/h
7.7
8.5
9.4
10.2
Pellet bin on boiler (net)
kg
220 kg (1078 kWh)
Maximum distance to pellet store
m
20
Ash box volume
litres
94
Flue gas mass flow rate, partial / full load
g/s
41 / 120
45 / 130
48 / 139
51 / 148
CO
2
content in dry exhaust gas partial/full load
%
11.1 / 13.2 11.2 / 13.4 11.2 / 13.7 11.3 / 13.9
Exhaust temperature at partial / full load
°C
~70 / ~130
Required flue draught
Pa
> 5 Pa
A draught limiter is always required (≤15 Pa)
Carbon monoxide (CO) emissions at partial / full load
mg/MJ
19 / 2
19 / 2
18 / 2
18 / 2
mg/m³
(13% O
2
)
29 / 3
29 / 3
28 / 3
27 / 3
Dust emissions at partial/full load
mg/MJ
8 / 6
7 / 6
7 / 6
7 / 7
mg/m³
(13% O
2
)
11 / 9
11 / 9
11 / 10
11 / 10
Unburned hydrocarbon emissions (CxHy) at partial/
full load
mg/MJ
1 / <1
1 / <1
1 / <1
1 / <1
mg/m³
(13% O
2
)
1 / <1
1 / <1
1 / <1
1 / <1
Electrical power consumption at partial/full load
(=values with integrated precipitator)
W
78 / 227
(358 / 487)
Electrical power consumption in ready mode
W
17
Maximum permissible operating pressure
bar
3
Temperature adjustment range
°C
70 – 90
Maximum permissible operating temperature
°C
95
Boiler class
5 acc. to EN 303-5:2012
Suitable fuels
Pellets ISO 17225-2-A1, ENplus-A1
Electrical connection
230 V AC / 50 Hz / 16 A
Mode of operation
non-condensing
Содержание 13180 LP-D
Страница 1: ...2020 04 21 EN 0000000475 V 006 5402 00 939091 002 Pellet boiler ePE K 180 240 kW Installation ...
Страница 33: ...Buffer storage tank Connection between multiple buffer storage tanks 33 ...
Страница 55: ...Installation Network connection 55 ...
Страница 61: ...Electrical connections Overview of circuit boards 61 ...
Страница 65: ...Electrical connections Circuit board HA C5 65 ...
Страница 85: ......
Страница 86: ...www eta co at ...
Страница 87: ......
Страница 88: ...www eta co at www eta co at downloads DOWNLOAD ...