Requirements
Electrical connections
10 Electrical connections
10.1
Requirements
Electrical connection must only be made by
qualified specialist personnel
The electrical installation must only be performed
by specialist personnel with the corresponding
qualifications.
Requirements
Observe the regulations and special regulations of
local energy utilities.
For full separation according to the setup require-
ments, a separating device of overvoltage
category III must be installed in the permanent
electrical installation. In most cases, these require-
ments are fulfilled with a circuit breaker, for example.
For speed-controlled pumps (controled via PWM-
signal), the maximum cable lengths of the pump
manufacturer must be observed.
Maximum outputs
WARNING!
Earthing of the boiler is required
Separate earthing is required for the boiler.
To do so, a connection must be established
between the boiler and the structural
potential equalisation in the boiler room
(minimum cross-section 6 mm²).
DANGER!
Do not carry out work on high voltage units
The housing of the high voltage unit may
not be opened or damaged as there are
parts inside it that are under high voltage.
Non-compliance with the above may
result in serious or fatal injuries.
DANGER!
Electric shock
There are live parts on the circuit boards. If
touched, they can cause injury and
property damage.
Before beginning any work, isolate the system
completely from all power sources, ensure that it
cannot be switched back on, and verify that it is
safely isolated from supply.
CAUTION!
Flexible stranded conductors
If flexible stranded conductors are not used for the
wiring, the contacts in the plug connections will be
subjected to excessive mechanical strain. In this case,
the warranty for the electronics would become null and
void.
Only flexible stranded conductors may be used for
the wiring.
Mains protection
C 16
Mains connection
3 x 1.5²
Type of supply cable
H05VV-F 3G 1.5
230 VAC components:
1.0²
Temperature sensors:
0.5² - 1.0²
230 V output
Maximum
power
A single output
250 W
Sum of all outputs
700 W
Potential-free output
(special function)
Maximum
switching capac-
ity
A single relay output
500 W
Содержание 13180 LP-D
Страница 1: ...2020 04 21 EN 0000000475 V 006 5402 00 939091 002 Pellet boiler ePE K 180 240 kW Installation ...
Страница 33: ...Buffer storage tank Connection between multiple buffer storage tanks 33 ...
Страница 55: ...Installation Network connection 55 ...
Страница 61: ...Electrical connections Overview of circuit boards 61 ...
Страница 65: ...Electrical connections Circuit board HA C5 65 ...
Страница 85: ......
Страница 86: ...www eta co at ...
Страница 87: ......
Страница 88: ...www eta co at www eta co at downloads DOWNLOAD ...