84
www.eta.co.at
Fire safety regulations
Pellet store
Minimum clearances for outdoor fuel stores:
•
When setting up a pellet storage container
in open air, maintain clearances from buildings and
property boundaries according to state building
legislation.
Temperature monitoring system in fuel store/pellet
bin:
•
In accordance with TRVB H 118, an alarm
thermostat must be installed above the conveying
hose where it exits the fuel store, or the pellet bin.
This alarm thermostat is not required for an ETA
pellet system since the ETA rotary valve with
pressure equalisation ensures that no gas can flow
in either direction between the combustion
chamber and the fuel store. This has been
confirmed by tests at the Institut für Brandschutz-
technik und Sicherheitsforschung (institute for fire
protection engineering and safety research) in
Linz.
Fire safety regulations in Germany
In Germany, the specimen ordinance on combustion
equipment (Muster-Feuerungsverordnung MFeuVO,
version dated September 2005) is the basis for fire
safety regulations. Below are the most important rules
from these regulations. Since there are minor
variations among the states, get information from
specialists such as the local master chimney sweep.
Pellet stores up to 10,000 litres / 6.5 tons:
•
Here there are no requirements for walls, ceilings
and doors and no usage restrictions are stipulated.
Pellet stores over 10,000 litres / 6.5 tons:
•
Walls and ceilings REI90 (F90).
•
no lines through walls,
•
No other use.
•
Doors self-closing and fire-resistant EI30 (T30).
•
Pellet filling lines through other rooms EI90 (F90).
Rated heat output of boiler less than 50 kW (boiler
room):
•
No requirements for the room.
•
Not permitted: installation in required stairwells, in
rooms between required stairwells and exits to the
outside, and in required hallways (escape routes).
•
Boilers with external air supply (PelletsUnit and
PelletsCompact 20-32 kW) may be installed in
garages (does not apply for Baden-Württemberg,
Saarland and Rhineland-Palatinate).
•
Up to 10,000 litres of pellets may be stored in
boiler room; clearance between heating appliance
and fuel store 1 m or sheet metal heat deflector
Rated heat output of boiler over 50 kW (boiler
room)
•
Headroom at least 2 m and room volume at least
8 m³.
•
Walls and ceilings REI90 (F90).
•
Self-closing, fire-resistant doors EI30 (T30) that
open in direction of escape.
•
Up to 10,000 litres of pellets may be stored in
boiler room; clearance between heating appliance
and fuel store 1 m or sheet metal heat deflector.
•
No other use.
•
For pellet-conveying hoses through rooms outside
the boiler room (fire compartment), fire-resistant
collars must be installed in the wall openings facing
the boiler room.
•
Ventilation lines through other rooms EI90 (F90).
•
Fire extinguishers as initial firefighting aids are
only legally regulated for commercial and public
buildings.
Содержание 13180 LP-D
Страница 1: ...2020 04 21 EN 0000000475 V 006 5402 00 939091 002 Pellet boiler ePE K 180 240 kW Installation ...
Страница 33: ...Buffer storage tank Connection between multiple buffer storage tanks 33 ...
Страница 55: ...Installation Network connection 55 ...
Страница 61: ...Electrical connections Overview of circuit boards 61 ...
Страница 65: ...Electrical connections Circuit board HA C5 65 ...
Страница 85: ......
Страница 86: ...www eta co at ...
Страница 87: ......
Страница 88: ...www eta co at www eta co at downloads DOWNLOAD ...