Safety
General information
15
6
Safety
6.1
General information
Operation only by trained personnel
The product may be operated by trained adults only.
Training may be provided by the heating technician or
our customer service. Please read the associated doc-
umentation carefully in order to avoid errors during
operation and maintenance.
Persons who lack experience and knowledge as well
as children may not operate, clean, or maintain the
product.
Keep children away from the pellet store
Children must be kept away from the pellet store. It is
a good idea to lock the door to the pellet store. The
door handle on the inside of the pellet store must not
be removed. It must be possible to open the door from
the inside in an emergency.
Keep fire extinguishers in a clearly visible location
In Austria, the minimum requirement is an
ABC powder extinguisher with 6 kg. An AB foam extin-
guisher with 9 litres, which produces less damage
when used, is preferable. The fire extinguisher should
be kept outside the boiler room, visible and easily
accessible. Even if country-specific regulations do not
prescribe a fire extinguisher, we still recommend that
you keep one in-house.
Fig. 6-1: Fire extinguisher
Storage of ash
The ash must be kept in non-flammable containers
with covers for cooling. Never put hot ash into the
waste bin!
DANGER!
Do not carry out work on high voltage units
The housing of the high voltage unit may
not be opened or damaged as there are
parts inside it that are under high voltage.
Non-compliance with the above may
result in serious or fatal injuries.
DANGER!
Caution high voltage!
The electrode inside the precipitator can
still have residual voltage even after
switching off the power supply.
Therefore, switch off the boiler at the
mains switch and ensure that it cannot be switched
back on before starting work. Then establish
additional earthing between the electrode on the
inside and the housing of the precipitator.
6.2
Safety devices
Pump safety run, automatic heat dissipation at
overtemperature
If the boiler temperature exceeds 90°C (factory setting)
for any reason, the pump safety run will start. All
heating pumps and boiler pumps that are connected to
the boiler control system are switched on to dissipate
heat from the boiler.
This action prevents the boiler temperature from rising
further and triggering further safety devices such as
the safety temperature limiter and the thermal relief
valve.
The heat dissipation is limited by the maximum
flow temperature set in the heating circuits and
the target hot water temperature.
Содержание 13180 LP-D
Страница 1: ...2020 04 21 EN 0000000475 V 006 5402 00 939091 002 Pellet boiler ePE K 180 240 kW Installation ...
Страница 33: ...Buffer storage tank Connection between multiple buffer storage tanks 33 ...
Страница 55: ...Installation Network connection 55 ...
Страница 61: ...Electrical connections Overview of circuit boards 61 ...
Страница 65: ...Electrical connections Circuit board HA C5 65 ...
Страница 85: ......
Страница 86: ...www eta co at ...
Страница 87: ......
Страница 88: ...www eta co at www eta co at downloads DOWNLOAD ...