AXX 9100 CONNECT R1.2 Quick Reference Guide
3/1531-ZAP 701 14/1 Uen A 2006-10-16
2
•
The site conforms to all environmental specifications
•
The floor or mounting area where you will install the equipment
can support the equipment.
N O T E !
The following tables are based on typical AXX 9100
CONNECT system configurations and may vary in specific
customer configurations.
1.
Power supply for the AXX 9100 CONNECT equipment must be
available as described in Table 1
2.
Power consumption for the AXX 9100 CONNECT equipment
must be supported as described in Table 1
3.
Circuit breakers for the AXX 9100 CONNECT equipment must be
according to Table 1
4.
Recommended clearance for accessing the AXX 9100
CONNECT equipment during and after installation must be as
described in Table 2 :
Table 1 Power Supply Requirements
Table 2 Recommended Access Clearance
1.3
Unpacking
When unpacking and storing AXX 9100 CONNECT equipment:
•
Leave equipment packed until it is needed for immediate
installation.
•
Store packed equipment in a ventilated and static-safe location
Equipment Type
Power Supply Requirements
-48 V DC
- 48 VDC; -36 to -72 V DC
Power consumption capability
50 W
Circuit breaker requirement
2 A
Item
Recommended Clearance
Bay access needed for maintenance
Front access only, 500 mm
Back clearance to bays (if necessary)
300 mm