7
3/1531-ZAP 701 14/1 Uen A 2006-10-16
AXX 9100 CONNECT R1.2 Quick Reference Guide
•
Multimeter
•
Pozidrive screwdriver (PZ3, PZ) to attach the AXX 9100
CONNECT to the rack and to attach the brackets to the AXX
9100 CONNECT,
•
Phillips (PH3) as an alternative screwdriver
•
Allen wrench
•
Yellow green flexible ground cable (1.25 - 2.50 mm
2
, 16 - 14
AWG)
•
1.25mm lint-free swabs (preferably clean room quality)
•
Video fiber connector inspection instrument
•
Caps for optical connectors
•
Plugs for optical adapters
•
Tie wraps
1.4.3
Installation Guidelines
When installing AXX 9100 CONNECT equipment into racks, follow
these guidelines:
•
Consider the effect of additional electronic equipment and its
generated heat on the AXX 9100 CONNECT system equipment.
•
Make sure the equipment rack is properly bolted to the ground
and, if required, to the ceiling.
•
Ensure that the weight of the equipment does not make the rack
unstable.
•
When mounting the equipment between two posts or rails,
ensure that the minimum clearance between the sides is 19 “.
•
Maintain a minimum clearance of 500 mm in front of the
equipment and 300 mm at the back of the equipment.
1.4.4
Grounding Considerations
We recommend a proper grounding of the AXX 9100 CONNECT
independent on safety requirements. The AXX 9100 CONNECT
may be connected to ground with the yellow/green wire in the power