AXX 9100 CONNECT R1.2 Quick Reference Guide
3/1531-ZAP 701 14/1 Uen A 2006-10-16
8
cable (pin on power connector marked GND), or by permanently
connection of the chassis to ground.
For location of the power connector on the AXX 9100 CONNECT,
see Figure 1
Figure 1 Location of the power connector on the AXX 9100 CONNECT
1.4.5
Power Interfaces
The AXX 9100 CONNECT DC-power interface comply with
ETSI/EN 300 132-2, with a nominal source voltage of -48VDC or -
60VDC. This covers the a voltage range from -40VDC to -72VDC.
If installed outside a RAL, use a power source with a maximum
voltage of -60VDC.
1.5
AXX 9100 CONNECT Installation
Use the following procedures to install the AXX 9100 CONNECT in
an equipment rack.
When installing the AXX 9100 CONNECT, you can also use the
extension brackets, included in the AXX 9100 CONNECT accessory
kit, to convert a 19-inch rack to a ETSI rack.
N O T E !
1U is 44.45 mm.