Cabin lighting
Fan
Lighting can be installed anywhere, however
not near rising hot air or hot steam. The light
output in the relay box is set to inductive load
by default, but light bulbs, halogen HV bul-
bs and other resistive loads may also be con-
nected to it. If required, the light output can
also be manually set to capacitive loads.
For light configuration see „Manual light confi-
guration“ chapter.
Cabin lighting is not included in the scope of
delivery. Observe the separateinstallation in-
structions for lighting.
Requirements to cabin lighting
• Lighting must be dimmable
• Minimal power output 5 W
• Resistive loads max. 100 W
• Dimmable energy-saving lamps max. 35 W
• Light sources with conventional transfor-
mers max. 60 VA
The relay box features an output for a fan. A
ventilation fan can be connected and operated
using this output.
The fan is not included in the scope of delivery.
Observe the separate installation instructions
for the fan.
For connection please refer to the chapter
„Electric Connections“.
Requirement to a fan
• Minimal power 5 W
• Maximum power 150W
• Voltage 230 V 1N AC
• Suitable for installation in humid condi-
tions (IP65)
• Only fans without starting capacitor
NOTICE
Material damage by unsuitable lamps or installation place
Lighting and the control panel could become damaged if nondimmable light sources are installed.
In this case, the warranty becomes void.
• Do not install the lighting in areas with rising hot air or hot steam.
• The lighting must conform to protection class IPX4 in saunas / IR cabins or IP65 in steam
rooms / hammams and be resistant to ambient temperatures.
• Connect only dimmable light sources.