From the firmware R3.57 the setup of the HOME function can be reached directly during the initial
setup of the sauna control unit (note the KNX or Modbus module must be connected to the con-
trol unit and must be operational).
From factory the sauna control unit is supplied with the HOME function set to „disabled“.
Setup for remote operation via SBM-GLT-KNX module:
• Make sure the SBM-GLT-KNX module is connected and operational.
• Make sure that during the initial setup it has been confirmed that the sauna is compliant with
the legal requirements for remote control (availability of the approved safety system).
• Open „Home“ setup menu either during the inital setup (from Firmware R3.57) or via the
„Home“ icon in the service level settings. Open the submenu „KNX“.
• Enable (activate) KNX remote control. The setup is herewith complete, exit the menu.
Setup for remote operation via SBM-GLT-Mod module:
• Make sure the SBM-GLT-Mod module is connected and operational.
• Make sure that during the initial setup it has been confirmed that the sauna is compliant with
the legal requirements for remote control (availability of the approved safety system).
• Open „Home“ setup menu either during the inital setup (from Firmware R3.57) or via the
„Home“ icon in the service level settings. Open the submenu „Modbus“.
• Enable (activate) the remote control for Modbus systems.
• Make the additional individual settings for the Modbus system. The parameters should be
provided by the Modbus provider / IT-specialist.
• Parameters: Address, Stop bits, Parity, Baud Rate.
Default setting: Address 247, 1 Stop bit, No parity, Baud Rate 19200.
• Confirm your setting. The setup is herewith complete, exit the menu.
You can change these settings at any time via the service level menu. For additional information
about installation and setup of the KNX or Modbus modules please refers to their corresponding
installation and operation manuals.
Back (exit service level)
Select and press the
symbol in order to exit the service level. Alternatively you can shortly
press the “Home“ button (on/off button).
The service level will be automatically closed, if you do not operate the control unit for 15 seconds.
The control panel will then return to the start screen.