36
EN
Setting the jumper for
maximum heating time
The sauna heater‘s heating time is limited dur-
ing installation by the jumper setting. The actu-
al runtime can be adjusted on the control panel
within the limits of the jumper setting.
Heating time of max. 6 h for
private use
Heating time of max. 12 h for
commercial use without mon-
itoring
Heating time of max. 18 h for
commercial use without mon-
itoring
Heating time of 24 h for 7 days
For this setting, the heating
time must be switched off
manually.
The setting is permitted only if
the sauna is used commercial-
ly and monitored.
Setting JP5 jumper for heating time
•
WARNING! Ensure that the relay box has
no power. Open the housing.
• Set jumper JP5 to the desired runtime.
JP5
JP5
Connecting data line
WARNING! Ensure that the relay box has
no power. Open the housing.
• Removing the housing cover.
• Route the line through the openings at the
base or on the back of the housing.
• The main relay box must be connected to the
control panel.
• For connection of the control panels use
the S-Bus cable RJ10/RJ14 (5 m, longer lines
optionally available) and connect it to a free
RJ12 S-Bus connector in the main relay box.
• Connect an optionally available extension
module using the S-Bus cable RJ12/RJ12 to
a free RJ12 S-Bus connector in the main relay
box. Use a modular coupler if necessary.
• Only connect the power supply after all data
lines have been properly connected.
Sensor-Bus RJ10 for sensors
Sauna-Bus RJ12 for display
panel and modules