13
EN
Installation
This chapter describes how to install the relay box and the most important components.
Cables with the appropriate cross section should be used for the heater, vaporizer (steam genera-
tor) or an other heating system, as well the light, fan and other components.
All electrical installations and all connecting lines that are installed inside a cabin must be suitable
for a use in a sauna / IR cabin (IPx4 class) or in a steam room / hammam (IP 65). All lines must be
routed in such a way that they are well-protected, e.g. in a cable duct.
NOTICE
NOTICE
Damage due to incorrect mounting location
The control unit is not suitable for outdoor use!
• It must be operated only inside buildings and may not be exposed to environmental conditions
such as extreme humidity and moisture or the possible formation of condensation or corrosive
substances in the ambient air, as well as other weather conditions.
• Similarly, excessive cold and extreme exposure to sunlight must be prevented.
• Protect the unit accordingly if there is an increased risk of mechanical damage.
Electronics malfunctions
Routing data and power supply lines together can lead to electronics malfunctions because, e.g.
because the sensor will not be detected.
• Do not route sensor and sauna bus lines together with power supply lines.
• Route separate cable conduits.
Site requirements
• Ambient temperature during operation -10°C to 35°C
• Relative air humidity during operation 30% to 75%
• Ambient air may not be corrosive or have high salt content
• Storage temperature -20°C to +60°C
• Stable wall able to carry unit‘s weight
• Power supply 400 V 3N ~ 50 Hz nearby
• All cable lines and connections must be accessible for servicing.