Software Release: [App: 02.09.10039.00; Config: 2.9.20024; Built in PowerVision Configuration Studio Version:
2.9.23042; BTL: 02.09.10015.00]
Section 40
46
00-02-0996
2019-06-13
by decreasing the RPM below the deadband and increasing the RPM above the deadband to
maintain the desired level of Pressure.
Factory set to Discharge.
Line Fill 1 Speed
–
(Medium Security): the engine is throttled to this speed after warm-up to purge
the line.
Factory set to 900 RPM.
Line Fill 1 Delay
–
(Medium Security): the time the engine is held at the Line Fill 1 speed.
Factory
set to 00.00.00.
Line Fill 1 Pressure
–
(Medium Security): the engine is held at the Line Fill 1 Speed until either this
pressure set point is reached or the Line Fill 1 Delay expires.
Factory set to 0 psi.
Line Fill 2 Speed
–
(Medium Security): present when Hose Reel is selected in the Applications menu.
The engine is throttled to this speed after Line Fill 1 to fill the line.
Factory set to 900 RPM.
Line Fill 2 Delay
–
(Medium Security): present when Hose Reel is selected in the Applications menu.
This is the time the engine is held at the Line Fill 2 speed before advancing to pressure throttle
control.
Factory set to 00.00.00.
Line Fill 2 Pressure
–
(Medium Security): present when Hose Reel is selected in the Applications
menu. The engine is held at the Line Fill 2 Speed until either this pressure set point is reached or
the Line Fill 2 Delay expires before advancing to pressure throttle control.
Factory set to 0 psi.
Pressure P
–
(High Security): This selection is present when PID Auto Throttle Type selected and
allows adjustment of the Proportional setting of the PID loop when throttling.
Factory set to 0.020
Pressure I
–
(High Security): This selection is present when PID Auto Throttle Type selected and
allows adjustment of the Integral setting of the PID loop when throttling.
Factory set to 0.020
Pressure D
–
(High Security): This selection is present when PID Auto Throttle Type selected and
allows adjustment of the Derivative setting of the PID loop when throttling.
Factory set to 0.001
Flow Transducer
–
(Medium Security): only present when selecting Flow Transducer in the Auto Start / Stop
Function or Auto Throttle Method.
Start Flow Rate
–
(Medium Security): present when selecting Flow Transducer as the Auto Start /
Stop Function. When the flow reaches this set point, an auto start will occur.
Factory set to 0
gpm.
Stop Flow Rate
–
(Medium Security): present when selecting Flow Transducer as the Auto Start /
Stop Function. When the flow reaches this set point, an auto stop will occur.
Factory set to 0
gpm.
Maintain Flow
–
(Medium Security): engine will be throttled between the min. and max. RPM set
points to maintain this flow.
Factory set to 0 gpm.
Steady / Proportional
–
(Medium Security): present when PID Auto Throttle Type is selected. Steady
throttles the engine to the max. RPM set point when starting and stopping on flow. Proportional
throttles the engine proportionally between the min. and max. RPM set points when starting and
stopping on flow. 0 gpm must be selected in the maintain flow for the steady/proportional features
to work.
Factory set to Steady.