Deadband Flow
–
(Medium Security): extends above and below the maintain set point. No throttling
occurs while the flow is in the deadband.
Factory set to 0 gpm.
Flow Type
–
(Medium Security):
In / Out.
In:
when the Auto Start/Stop is selected as Flow Transducer and the Flow Type is set to
(In)
, it is
necessary to set the flow to start on a low value
(falling ↓) then stop on high value (rising ↑) in order
to work correctly. When the Auto Throttle Method is selected to Flow Transducer and the Flow
Type is set to
(In)
, the controller throttles the engine by increasing the RPM below the deadband
and decreasing the RPM above the deadband to maintain the desired level of Flow.
Out:
when the Auto Start/Stop is selected as Flow Transducer and the Flow Type is set to
(Out)
, it
is necessary to set the flow to start on a high value
(rising ↑) then stop on low value (falling ↓) in
order to work correctly. When the Auto Throttle Method is selected to Flow Transducer and the
Flow Type is set to
(Out)
, the controller throttles the engine by decreasing the RPM below the
deadband and increasing the RPM above the deadband to maintain the desired level of Flow.
Factory set to Out.
Flow P
–
(High Security): This selection is present when PID Auto Throttle Type selected and allows
adjustment of the Proportional setting of the PID loop when throttling.
Factory set to 0.020
Flow I
–
(High Security): This selection is present when PID Auto Throttle Type selected and allows
adjustment of the Integral setting of the PID loop when throttling.
Factory set to 0.020
Flow D
–
(High Security): This selection is present when PID Auto Throttle Type selected and allows
adjustment of the Derivative setting of the PID loop when throttling.
Factory set to 0.001
Level Transducer
–
(Medium Security): only present when selecting Level Transducer in the Auto Start / Stop
Function or Auto Throttle Method.
Start Level
–
(Medium Security): present when selecting Level Transducer as the Auto Start / Stop
Function. When the level reaches this set point, an auto start will occur.
Factory set to 0.0 ft.
Stop Level
–
(Medium Security): present when selecting Level Transducer as the Auto Start / Stop
Function. When the level reaches this set point, an auto stop will occur.
Factory set to 0.0 ft.
Maintain Level
–
(Medium Security): the engine will be throttled between the min. and max. RPM set
points to maintain this level.
Factory set to 0.0 ft.
Deadband Level
–
(Medium Security): extends above and below the maintain set point, no throttling
occurs while the level is in the deadband.
Factory set to 0.0 ft.
Steady / Proportional
–
(Medium Security): present when PID Auto Throttle Type is selected. Steady
throttles the engine to the max. RPM set point when starting and stopping on level. Proportional
throttles the engine proportionally between the min. and max. RPM set points when starting and
stopping on level. 0.0 ft must be selected in the maintain level for the steady/proportional features
to work.
Factory set to Steady.
Level Type
–
(Medium Security):
Fill / Empty
.
Fill:
when the Auto Start/Stop is selected as Level Transducer and the Level Type is set to
(Fill)
, it
is necessary to set the flow to start on a low value
(falling ↓) then stop on high value (rising ↑) in