Software Release: [App: 02.09.10039.00; Config: 2.9.20024; Built in PowerVision Configuration Studio Version:
2.9.23042; BTL: 02.09.10015.00]
Section 40
31
00-02-0996
2019-06-13
Engine Manufacturer
(High Security)
:
allows the selection of the specific engine manufacturer (i.e.,
Caterpillar (M-T4F), Cummins (M-T4F), John Deere (M-T4F), Deutz (M-T4F), Kohler KDI 1903, Kubota (M-
T4i, Gaseous), JCB (T4F), Volvo (T3-T4F), FPT (T4F), Isuzu (M), PSI (EControls ECU), Scania (T3-T4F),
FORD (EControls ECU), Perkins (M-T4F), Other, HATZ (M-T4F), GM (MEFI ECU), Yanmar (T4F).
Factory
set to Other.
Engine Emission
–
(High Security):
allows the selection of the emissions of the engine (i.e., Tier 3 or less,
Interim Tier 4, or Tier 4 / EU Stage IIIA, IIIB, IV).
Factory set to Tier 3 or Less.
Tier 4
(Low Security)
:
(only appears if Interim Tier 4 or Tier 4 / EU Stage IIIA, IIIB, IV is chosen) allows
the automatic or inhibition of after treatment regeneration and/or the requesting of a regeneration.
Auto/Inhibit regen
(Low Security)
:
allows the operator to inhibit an after treatment regeneration
by setting to inhibit.
Factory set to Auto
Request Regen
(Low Security)
: s
ends a request to the engine ECU for regeneration.
Factory
set to No
DEF Gauge
(High Security)
: s
hows the DEF gauge when set to Yes.
Factory set to No
Percent Soot Gauge
(High Security)
:
shows the % Soot gauge when set to Yes.
Factory set to
No
Regen Screen
(High Security)
:
shows the regeneration screen in the main screens when set to
Yes.
Factory set to No
NOTE:
Inhibiting the Regen may cause the engine to de-rate or shut down if the soot level is
too high. Recommend leaving this setting in Auto Regen. The ECU may not allow the
Regen request if certain parameters do not meet the engine manufacturers
’ requested
levels.
Speed Source
–
(High Security): allows the selection of the appropriate speed source of the engine (i.e.,
J1939, Alternator or Magnetic Pickup).
Factory set to J1939.
Speed Calibration
– Pulse Count
(High Security): allows the setting of the correct number of flywheel teeth
or engine alternator pulses for mechanical engines. When Speed Source is set to J1939, the Speed
Calibration menu is hidden.
Factory set to 150.0.
Speed Calibration
– RPM
(High Security): allows user to set the known RPM speed of the engine while
running to calculate backwards to a pulse count from the alternator or flywheel gear.
Minimum Engine Speed
–
(Medium Security): allows the setting of the lowest engine speed for the running
loaded state. The controller will not allow the engine to throttle under the minimum engine speed during this
state.
Factory set to 700 RPM.
Maximum Engine Speed
–
(Medium Security): allows the setting of the highest engine speed for the running
loaded state. The controller will not allow the engine to throttle above the maximum engine speed during this
state.
Factory set to 2200 RPM.
Warm Up Speed
–
(Medium Security): allows the setting of the engine speed during the warm-up state.
Factory set to 900 RPM.