Auto Stop Delay
–
(Medium Security): auto stop condition must remain active throughout this delay
for an auto stop to occur. If the auto stop condition is removed during this delay, the delay is reset to
zero.
Factory set to 3 seconds.
Minimum Run Time
–
(High Security): if an auto start condition started the engine, the auto stop
condition is ignored until this delay times out.
Factory set to 00.00.00
ECU Stabilize Timer
–
(High Security): on startups, this delay allows the ECU to stabilize and
broadcast on the CAN bus prior to actual cranking.
Factory set to 5 seconds.
Crank Time
–
(High Security): length of time the crank output is turned on during cycle cranking.
Factory set to 10 seconds.
Crank Rest
–
(High Security): length of time the crank output is turned off during cycle cranking.
Factory set to 10 seconds.
Prestart Delay 1
–
(Low Security):
Auto Only
–
(Medium Security): allows the selection of having Prestart #1 active during auto
only. Choose from Enabled or Disabled.
Factory set to Disabled.
Prestart Delay 1
–
(Low Security): after an auto start condition has been accepted by the
controller, this delay begins timing, and the prestart #1 output turns on. When this delay
expires, the output is turned off, and the auto sequence continues.
Factory set to 00.00.00
Prestart Delay 2
–
(Low Security):
Auto Only
–
(Medium Security): allows the selection of having Prestart #2 active during auto
only. Choose from Enabled or Disabled.
Factory set to Disabled.
Prestart Delay 2
–
(Low Security): after an auto start condition has been accepted by the
controller, this delay begins timing, and the prestart #2 output turns on. When this delay
expires, the output is turned off, and the auto sequence continues.
Factory set to 00.00.00
Prestart Delay 2 Mode
–
(High Security): determines if the prestart #2 output is active through the
crank state or only through the prestart #2 state.
Factory set to PreCrank.
Energize to Stop Time
–
(High Security): begins timing and an output is turned on after an auto stop
condition has been accepted by the controller. The output is turned off when this delay expires.
NOTE:
If the controller is turned off by disconnecting power, this feature will be skipped in the shut-down
sequence.
Factory set to 00.00.00
Spindown Timer
–
(Medium Security): begins timing after the cool-down delay to remove the ECU
Enable/Fuel output to allow the shutdown of the engine. This state allows the engine to get to 0 RPM
prior to allowing the engine to crank. This timer will repeat if RPM is present when the timer completes
its countdown.
Factory set to 30 seconds.
Post Crank Lockout Setup
–
(Medium Security): allows a delay that begins timing when the engine
starts. During this delay, the selected functions (Warnings and Shutdowns) are ignored. When this
delay expires, the selected functions are armed. During the duration of this delay, the selected
functions can cycle from active to not active and not reset the delay.
Post Crank Lockout Time
–
(Medium Security):
Factory set to 30 seconds.