Software Release: [App: 02.09.10039.00; Config: 2.9.20024; Built in PowerVision Configuration Studio Version:
2.9.23042; BTL: 02.09.10015.00]
Section 40
35
00-02-0996
2019-06-13
LOP Shutdown/High Speed
–
(High Security): Low Oil Pressure (LOP) setting in which the controller
will provide a shutdown if dropping below at high speed.
Factory set to 30.00 psi.
Low Oil Pressure Warning
–
(High Security): sounds a warning when the oil pressure reaches the
set lower limit parameter for oil pressure.
Factory set to 15.00 psi.
Low Oil Pressure Shutdown
–
(High Security): shuts down the engine when the oil pressure reaches
the set lower limit parameter for oil pressure.
Factory set to 10.00 psi.
High Oil Temp Warning
–
(Medium Security): sounds a warning when the oil temperature reaches
the set higher limit parameter for oil temperature.
Factory set to 210 °F.
High Oil Temp Shutdown
–
(Medium Security): shuts down the engine when the oil temperature
reaches the set higher limit parameter for oil temperature.
Factory set to 225 °F.
High Oil Pressure Warning
–
(Medium Security): sounds a warning when the oil pressure reaches
the set higher limit parameter for oil pressure.
Factory set to 200.0 psi.
High Oil Pressure Shutdown
–
(Medium Security): shuts down the engine when the oil pressure
reaches the set higher limit parameter for oil pressure.
Factory set to 200.00 psi.
High Engine Temp Warning
–
(Medium Security): sounds a warning when the temperature of the
engine reaches the set higher limit parameter for temperature.
Factory set to 210 F.
High Engine Temp Shutdown
–
(Medium Security): shuts down the engine when the temperature
of the engine reaches the set higher limit parameter for temperature.
Factory set to 225 F.
Low Engine Temp Warning
–
(Medium Security): sounds a warning when the temperature of the
engine reaches the set lower limit parameter for temperature.
Factory set to 32 F.
Underspeed Shutdown
–
(Medium Security): shuts down the engine when the speed reaches the set
lower limit parameter for speed.
Factory set to 0 RPM.
Overspeed Shutdown
–
(Medium Security): shuts down the engine when the speed reaches the set
higher limit parameter for speed.
Factory set to 2400 RPM.
High Gearbox Pressure Warning
–
(Medium Security): sounds a warning when the gearbox
pressure reaches the set high limit parameter for gearbox pressure. Selection only shown when an
analog input is selected to monitor Gearbox Pressure.
Factory set to 0.00 psi.
High Gearbox Pressure Shutdown
–
(Medium Security): shuts down the engine when the gearbox
pressure reaches the set high limit parameter for gearbox pressure. Selection only shown when an
analog input is selected to monitor Gearbox Pressure.
Factory set to 0.00 psi.
Low Gear Box Pressure Warning
–
(Medium Security): sounds a warning when the gearbox
pressure reaches the set low limit parameter for gearbox pressure. Selection only shown when an
analog input is selected to monitor Gearbox Pressure.
Factory set to 0.00 psi.
Low Gear Box Pressure Shutdown
–
(Medium Security): shuts down the engine when the gearbox
pressure reaches the set low limit parameter for gearbox pressure. Selection only shown when an
analog input is selected to monitor Gearbox Pressure.
Factory set to 0.00 psi.