Proline Promass E 300 Modbus RS485
Electrical connection
Hauser
31
Signal damping
Max. 9 dB over the entire length of the cable cross-section
Shield
Copper braided shielding or braided shielding with foil shield. When grounding
the cable shield, observe the grounding concept of the plant.
Current output 0/4 to 20 mA
Standard installation cable is sufficient.
Pulse/frequency/switch output
Standard installation cable is sufficient.
Double pulse output
Standard installation cable is sufficient.
Relay output
Standard installation cable is sufficient.
Current input 0/4 to 20 mA
Standard installation cable is sufficient.
Status input
Standard installation cable is sufficient.
Cable diameter
• Cable glands supplied:
M20 × 1.5 with cable ⌀ 6 to 12 mm (0.24 to 0.47 in)
• Spring-loaded terminals: Suitable for strands and strands with ferrules.
Conductor cross-section 0.2 to 2.5 mm
2
(24 to 12 AWG).
Requirements for the connecting cable – Remote display and operating module
DKX001
Optionally available connecting cable
A cable is supplied depending on the order option
• Order code for measuring device: order code
030
for "Display; operation", option
O
or
• Order code for measuring device: order code
030
for "Display; operation", option
M
and
• Order code for DKX001: order code
040
for "Cable", option
A, B, D, E
Standard cable
2 × 2 × 0.34 mm
2
(22 AWG) PVC cable with common shield (2 pairs, pair-
stranded)
Flame resistance
According to DIN EN 60332-1-2
Oil-resistance
According to DIN EN 60811-2-1
Shielding
Tin-plated copper-braid, optical cover ≥ 85 %
Capacitance: core/shield
≤200 pF/m
L/R
≤24 µH/Ω
Available cable length
5 m (15 ft)/10 m (35 ft)/20 m (65 ft)/30 m (100 ft)
Operating temperature
When mounted in a fixed position: –50 to +105 °C (–58 to +221 °F); when cable
can move freely: –25 to +105 °C (–13 to +221 °F)